TROUBLESHOOTING
OFF-LINE FAILURE
6 - 10
I-E96-322A
®
Figure 6-3. Off-Line Failure Troubleshooting Flowchart
(Page 3 of 3)
DONE
NO
YES
NO
YES
NO
YES
NO
YES
TERMINAL
CONNECTIONS
CORRECT?
NO
YES
NO
YES
TU DIPSHUNTS
SET?
A2
HSS
OPERATING?
HSS
OPERATING?
SERVO VALVE
INSTALLED
PROPERLY?
NO
YES
HSS
OPERATING?
REPLACE THE HSS
MODULE
CHECK ACTUATOR
AND LVDT
INSTALLATION
AND CABLE
CHECK THE SERVO
VALVE AND CABLE
INSTALLATION
CONNECT FIELD
WIRING TO TU
TERMINALS
CORRECTLY INSTALL
THE DIPSHUNTS
TP25256B
LVDT AND
ACTUATOR INSTALLED
PROPERLY?
CONTACT
BAILEY CONTROLS
COMPANY
FOR ASSISTANCE