INTRODUCTION
I-E96-322A
B - 1
APPENDIX B - FUNCTION CODE 150 CALIBRATION
INTRODUCTION
covers the IMHSS03 calibration procedure using
function code 150, analog control loop tuning theory and the
controller gain tuning procedure. Completing the steps in this
appendix insures accurate positioning of the turbine throttle
valve and the best possible frequency response. Complete the
steps in this appendix before placing the hydraulic servo mod-
ule (HSS) in operation.
INITIAL CALIBRATION
Before beginning the module calibration procedure:
1. Obtain the following documents and have them on hand:
a.
Function Code Application Manual
b. The instruction manual for the operator interface (i.e.,
EWS, OIS, etc.).
2. Verify that the following conditions exist:
a. The valve (for turbine hydraulic system) must be in the
controlling position and functioning properly.
b. The controller or processor module has function
code 150 in its configuration.
c.
The HSS controller gain (dipswitch S3) is set to 1 (pole 8
is closed).
d. The HSS demodulator gain (dipswitch S2) is set to 2
(pole 8 is closed).
e.
The turbine should be off-line.
f.
If the turbine is on-line, there must be other controlling
valves operating to compensate for position changes of the
valve in calibration.
To calibrate the HSS module:
1. Verify that the block address specified in S7 contains the
proper number of calibration cycles (from 1 to 8).
2. Verify that the block address specified in S6 contains the
desired calibration cycle time. Values are 1 (30 seconds), 2 (60
seconds), 3 (35 minutes) and 4 (70 minutes). 30 and 60