ALLEN BRADLEY PLC
DIGITAL INPUT SUBSCRIBER (FC 185)
A - 4
WBPEEUI240759A0
®
DIGITAL INPUT SUBSCRIBER (FC 185)
Table A-3. FC 185 Outputs
%ON
7\SH
'HVFULSWLRQ
N
B
First digital input with quality
N+1
B
Second digital input with quality
N+2
B
Third digital input with quality
N+3
B
Fourth digital input with quality
N+4
B
Fifth digital input with quality
N+5
B
Sixth digital input with quality
N+6
B
Seventh digital input with quality
N+7
B
Eighth digital input with quality
Table A-4. FC 185 Specifications
Spec
Tune
Default
Type
Range
Description
S1
N
2
I
0 - 9998
Block address of next digital input subscriber block
S2
N
0.000
R
0 - 60000
Group identifier
1
S3
N
0
I
01 - 38
Subgroup number (x) and number of elements (y):
x = 0, 1, 2, or 3
y = 8
x
y
Spec
0
8
8
1
8
18
2
8
28
3
8
38
S4
N
0
I
0 - 3
Input type:
0 = digital
1 = digital with quality
S5
N
0.000
R
Full
PLC-5 file type and file number in xyyy format.
File type (x):
0 = binary
1 = input
2 = output
File number (yyy):
Binary file type = 0 - 999
Output file type = 000
Input file type = 001
S6
N
0.000
R
Full
Last two bytes of the PLC device IP address
S7
N
00
I
0 or 1
Not used
S8
N
00
I
00, 01, 10,
or 11
Scan class:
00 = 125 msec
01 = 250 msec
10 = 500 msec
11 = 1 sec
S9
Y
0.000
R
Full
PLC-5 element number: 0 - 999
S10
Y
0.000
R
Full
Spare
S11
Y
0.000
R
Full
Spare
NOTE:
1. The group identifier
must be unique for each group.