INTRODUCTION
SPECIFICATIONS
1 - 6
WBPEEUI240759A0
®
Power requirements
Operating power
5 VDC, ±5% at 1.8 A typical
+15 VDC, ±5% at 250 mA maximum
Power dissipation
10 W
Common mode isolation
500 V
rms
at 45 to 65Hz/1 min
Insulation resistance (100 VDC)
1.2M
Ω
Environmental
Ambient temperature
0° to 70°C (0° to 158°F) (noncondensing)
Relative humidity
10% to 90% up to 55°C (131°F)
10% to 45% from 56°C to 70°C (132°F to158°F) (noncondensing)
Atmospheric pressure
Sea level to 2.4 km (1.49 mi)
Air quality
Noncorrosive
Mounting
Occupies a single slot in a standard INFI 90 OPEN module mounting
unit (MMU)
Certification
(pending)
CSA certified for use as process control equipment in an ordinary
(nonhazardous) location.
Overvoltage (installation) category II
CE mark declaration
The product, when installed in an INFI 90 OPEN cabinet, complies with
the following directives/standards requested for CE marking:
EMC directive 89/336/EEC:
EN 50081-2 Generic emission standard - Part 2: Industrial environment
EN 50082-2 Generic immunity standard - Part 2: Industrial environment
Low voltage directive 73/23/EEC:
EN61010-1 Safety requirements for electrical equipment for measure-
ment, control, and laboratory use - Part 1: General requirement
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
Table 1-4. Specifications
(continued)
Property
Characteristic/Value