ALLEN BRADLEY PLC
FACTORY INSTRUMENTATION PROTOCOL HANDLER (FC 184)
A - 2
WBPEEUI240759A0
®
FACTORY INSTRUMENTATION PROTOCOL HANDLER (FC 184)
6SHFLILFDWLRQV
Explanation
S1
Specification S1 is the I/O expander bus address of the EDI
module.
S2
Specification S2 is not used; it must be set to a value greater
than 63.
S3
Specification S3 is the block address of the first analog input
subscriber (function code 186).
S4
Specification S4 is the block address of the first digital input
subscriber (function code 185).
S5
Specification S5 is the block address of the first analog output
subscriber (function code 187).
Table A-1. FC 184 Output
%ON
7\SH
'HVFULSWLRQ
N
B
Module status:
0 = good
1 = bad
N+1
B
Not used; always good
Table A-2. FC 184 Specifications
Spec
Tune
Default
Type
Range
Description
S1
N
0
I
0 - 63
IMEDI01 module address
S2
N
0
I
0 - 63
Must be set to a value greater than 63
S3
N
2
I
0 - 9998
Block address of analog input subscriber block
S4
N
2
I
0 - 9998
Block address of digital input subscriber block
S5
N
2
I
0 - 9998
Block address of analog output subscriber block
S6
N
2
I
0 - 9998
Block address of digital output subscriber block
S7
N
2
I
0 - 9998
Reserved
S8
N
0
I
0 - 9998
Reserved
S9
N
0
I
0 - 1
Must be set to 1
S10
N
0
I
–32767 -
32767
First two bytes of PLC device IP address
S11
N
0
I
0 - 60000
Reserved
S12
N
0
I
0 - 60000
Reserved
S13
N
0
I
0 - 100
Not used
S14
Y
0.000
R
Full
Not used
S15
Y
1.0
R
0.0 - 255.0
Not used
S16
Y
0.000
R
Full
Spare