FUNCTION CODE DEFINITIONS
ENHANCED ANALOG SLAVE DEFINITION FUNCTION CODE (FC 215)
C - 2
I-E96-301B
®
Table C-1. FC 215 Outputs
Block No.
Data Type
Description
N
REAL
Cold Junction Reference
Temperature (degrees C)
N+1
BOOLEAN
Slave Status: 0 = GOOD; 1 = BAD
N+2
REAL
Input scan cycle time (seconds)
Table C-2. FC 215 Output Descriptions
Block No.
Description
N
Temperature of the cold junction for reference inputs
as measured by the built-in RTDs on the termination
device of the IMASI03.
N+1
Indicates BAD if a failure of the slave is detected.
N+2
Represents the amount of time between successive
updates of an individual channel's input value and
quality.
Table C-3. FC 215 Specifications
Spec
No.
Tune
Default
Value
Data Type
Range
Min.
Max
Description
S1
No
0
INT(2)
0 to 63
Slave Address
S2
No
2
INT(2)
0 to 9998
Block Address of first Enhanced
Analog Input Definition (FC216)
S3
No
5
INT(2)
0 to 9998
Block Address of Cold Junction
Reference Input (degrees C)
S4
No
0
INT(2)
0 to 1
Failure Action
0 = Trip MFP
1 = Continue
S5
No
0
INT(2)
0 to 1
Normal Mode Rejection Type
0 = 60 Hz.
1 = 50 Hz.
S6
No
0
REAL(3)
Full
Termination Device Cable (feet)
S7
No
0
INT(2)
Full
Spare parameter
S8
No
0
INT(2)
Full
Spare parameter
S9
No
0
REAL(3)
Full
Spare parameter
S10
No
0
REAL(3)
Full
Spare parameter