INSTALLATION
SETUP/INSTALLATION
3 - 4
I-E96-301B
®
input. Set both jumpers on each input to pins 1 and 2 for a
voltage or current input. Each channel can be configured inde-
pendently. The IMASI03 can have any number of inputs config-
ured as resistance, low level voltage or high level voltage.
Table
lists the jumper configurations for the IMASI03.
lists the jumpers set to configure each channel on
the IMASI03. Figure
shows the jumper locations on the
IMASI03.
Table 3-2. IMASI03 Jumper Configurations
Analog Input Type
Jumper
Position
Jumper Number
Current
Thermocouples Low
Level Voltage
High Level Voltage
1 - 2
J1 - J32
(Analog Input 1 through
Analog Input 16)
3 Wire RTD
2 - 3
J1 - J32
(Analog Input 1 through
Analog Input 16)
Table 3-3. IMASI03 Jumpers Used for Each Channel
Channel
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Jumper
Number
J1
J2
J3
J4
J5
J6
J7
J8
J9
J10
J11
J12
J13
J14
J15
J16
J17
J18
J19
J20
J21
J22
J23
J24
J25
J26
J27
J28
J29
J30
J31
J32
Figure 3-2. IMASI03 Jumper Locations
STATUS
LED
EDGE
CONNECTORS
SW1
OPEN
7
6
2
3
4
5
1
8
INPUT
CELL 1
INPUT
CELL 16
P1
P3
P2
J31
J1
J2
3
1
2
J32
J2
J1
DEFAULTS
SW1
ADDRESS
SWITCH
SET JUMPER PAIR TO PINS 1 AND 2
FOR VOLTAGE AND CURRENT INPUT
SET JUMPER PAIR TO PINS 2 AND 3
FOR RESISTANCE INPUT
TP35255A