Modbus Register Addresses
Data Component Name
MODBUS Registers
Tvailable Units
Long Integer
Format
Floating Point
Single Precision
Format
Double Precision
Format
Signal Strength
40100 - 40101
40200 - 40201
40300 - 40303
Flow Rate
40102 - 40103
40202 - 40203
40304 - 40307
Gallons, Liters, MGallons, Cubic Feet, Cubic
Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet,
Meters, Lb, Kg, BTU, MBTU, MMBTU, TON, kJ,
kW, MW
Per Second, Minute, Hour, Day
Net Totalizer
40104 - 40105
40204 - 40205
40308 - 40311
Positive Totalizer
40106 - 40107
40206 - 40207
40312 - 40315
Negative Totalizer
40108 - 40109
40208 - 40209
40316 - 40319
Temperature 1
40110 - 40111
40210 - 40211
40320 - 40323
°C
Temperature 2
40112 - 40113
40212 - 40213
40324 - 40327
°C
Table 22: Flow meter modbus register map for ‘little-endian’ word order master devices
For reference: If the flow meters Net Totalizer = 12345678 hex
Register 40102 would contain 5678 hex (Word Low)
Register 40103 would contain 1234 hex (Word High)
Data Component Name
MODBUS Registers
Tvailable Units
Long Integer
Format
Floating Point
Single Precision
Format
Double Precision
Format
Signal Strength
40600 - 40601
40700 - 40701
40800 - 40803
Flow Rate
40602 - 40603
40702 - 40703
40804 - 40807
Gallons, Liters, MGallons, Cubic Feet, Cubic
Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet,
Meters, Lb, Kg, BTU, MBTU, MMBTU, TON, kJ,
kW, MW
Per Second, Minute, Hour, Day
Net Totalizer
40604 - 40605
40704 - 40705
40808 - 40811
Positive Totalizer
40606 - 40607
40706 - 40707
40812 - 40815
Negative Totalizer
40608 - 40609
40708 - 40709
40816 - 40819
Temperature 1
40610 - 40611
40710 - 40711
40820 - 40823
°C
Temperature 2
40612 - 40613
40712 - 40713
40824 - 40827
°C
Table 23: Flow meter modbus register map for ‘big-endian’ word order master devices
For reference: If the flow meters Net Totalizer = 12345678 hex
Register 40602 would contain 1234 hex (Word High)
Register 40603 would contain 5678 hex (Word Low)
Modbus Coil Description
Modbus Coil
Notes
Reset Totalizers
1
Forcing this coil on will reset all totalizers . After reset, the coil automatically returns to the off state .
Table 24: Modbus coil map
System Group
Page 81
November 2016
HYB-UM-00090-EN-04