background image

OPERATION

 

 
 
 
 

GENERAL DESCRIPTION 

 
  The Model 3000+ Micro-Chart Recorder is a circular 
chart recorder with microprocessor-based electronics. The 
unit is supplied with a LCD display for indicating rate 
and totalization. The rate is displayed with 4 digits and its 
multiplier and unit of measurement. The totalizer is 
displayed with 8 digits and its multiplier and unit of 
measurement. 

7

 

 
  The display is also used to program the recorder 
through menu driven prompts. The programming is 
activated via front panel keys. These keys also activate a 
Status Mode which will indicate if there are any alarms 
tripped and perform a self-test operation of the recorder. 
 
  The following will describe in detail the various 
functions of the Model 3000+ Recorder and programming 
steps to recalibrate the recorder in the field if necessary. 
 

INITIAL POWER UP 

 
  After installation and wiring of the Model 3000+ 
Recorder, power may be turned on by the power switch 
on the lower right hand corner of the chart plate. 
 
  When power is applied, the display screen will have a 
solid line across the top of the display for a few seconds. 
Then the following screen will appear: 
 
 

3000+ RECORDER 

BADGER METER INC 

 
 
  This screen informs the user of the Model of the 
recorder. This screen will be displayed for a few seconds. 
 
  The next screen to be displayed is the following: 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

SOFTWARE REVISION X.XX 

SERIAL NUMBER 12345678 

 
 
  This screen identifies the software revision the recorder 
is operating with and the serial number of the unit. This 
screen will be displayed for a few seconds. 
 
  The next screen shown is the screen that will be 
displayed during normal operation of the recorder. 
 
 

*FLOW  1234  X  10,000  GPM 

12345678   X  100,000 GAL 

 
 
  The top line displays the flow rate with its multiplier 
and the unit of measurement. The second line displays the 
totalized flow (4 or 8 digits) with its multiplier and unit of 
measurement. 
 
  The asterisk that is to the left of FLOW may or may not 
be present. If it is present, it indicates that an alarm has 
been tripped. The various alarms will be discussed in the 
Status Mode Section of this manual. 
 
  The recorder should be fully operational if there is an 
input signal from a transmitter. The recorder is 
programmed at the factory with the information supplied 
by the user and the Zero and Span have been calibrated. 
 
  If the flashing asterisk is present proceed to the Status 
Mode Section to determine the cause and proper action. 
 
  If the user desires to reset the Zero and Span or change 
any of the parameters of the recorder, proceed to the 
Calibration Section of this manual. 
 

Содержание 3000+

Страница 1: ...ng Diagram 20 UNPACKING INSPECTION To avoid damage in transit Eastech Badger products are shipped to the customer in special shipping containers Upon receipt of the product perform the following unpac...

Страница 2: ...or pressure or temperature totalization alarm indication and is used to program the recorder through menu driven prompts RECORDING 12 inch circular chart with 24 hour 7 day or 31 day selectable chart...

Страница 3: ...a window The door is provided with two lockable latches Caution should be used when mounting the enclosure so that it is not exposed to direct sunlight A sun shield is recommended to prevent the temp...

Страница 4: ...e dimensions If the outdoor enclosure has the window option do not mount facing the sun or install a sun shade to prevent overheatingoftheelectronicsinsidetheenclosure WIRING CONNECTIONS 4 20 MA OUTPU...

Страница 5: ...en the screws on the connectors Strip off about 1 4 inch of insulation from the wires Insert the wire into the proper connector and tighten the screw securely After connecting all of the wires to the...

Страница 6: ...ow not differential DC power must be connected in series with the load as shown above DRY CONTACT RELAYS MAX LOAD 250 MA 4 20 MA OUTPUT NO C SW 1 NC NO C SW 2 NC 1 2 3 4 5 6 7 8 TB5 RELAY OUTPUTS Rela...

Страница 7: ...reen informs the user of the Model of the recorder This screen will be displayed for a few seconds The next screen to be displayed is the following SOFTWARE REVISION X XX SERIAL NUMBER 12345678 This s...

Страница 8: ...tion of this manual CHT This indicates that the chart has made a complete rotation and the chart needs to be changed INT Indicates a contact integrator pulse output has occurred EE EEPROM read write e...

Страница 9: ...t the following screen will appear MEASUREMENTS UNITS UNIT INITIALS GPM This screen allows the user to select the engineering unit of measure for the flow rate To change the units press the UP or DOWN...

Страница 10: ...1 55 POWER 1 58 POWER 1 95 POWER 1 2 POWER 3 2 POWER 5 2 POWER OPTION The linear function is used where the transmitter output is proportional to flow The 1 55 power is used with 1 2 3 24 Parshall flu...

Страница 11: ...to be at the span value if the UP or DOWN arrow keys are not pressed When pressing the UP or DOWN arrow keys the display will indicate the direction of the pen movement Once the pen is positioned to s...

Страница 12: ...the channels to be summed must be input to the recorder when making this adjustment For example if the input signal is 4 20 mA for 0 to 100 then 4 mA must be input to all channels to be summed to mak...

Страница 13: ...t points If the High alarm is set for 60 percent and the hysteresis is 3 percent then the High alarm will trip closed at 63 percent and open at 57 percent Press the UP or DOWN arrow keys to the desire...

Страница 14: ...or DOWN arrow keys to select YES or NO and press the ENTER key The following screen will appear UNIT MULTIPLIER AAA X 1 000 This screen allows the selection of the desired flow rate multiplier Press...

Страница 15: ...reens appear during the chart pen adjusting procedure one of the following problems probably occurred 1 There was not a 4 20 mADC analog signal to the recorder analog channel you selected while adjust...

Страница 16: ...N OF DECIMAL WHOLE NUMBER TO HEXADECIMAL NUMBER 1 Divide the decimal number by 16 Example 57420 16 3588 75 2 Multiply only the fractional part of the product by 16 to arrive at the first character in...

Страница 17: ...lue of the next character Example 224 0 224 3 Multiply the previously found product by 16 Example 224 X 16 3584 4 Repeat steps 2 and 3 in a cyclical fashion until you have added the last hexadecimal c...

Страница 18: ...18 INSERT DWG 600662 9999 3000 RECORDER ASSY DWG...

Страница 19: ...15 SPACER 6 EA 2 0 34 400006 0025 SET SCREW 4 40 X 3 16 EA 1 0 35 524720 CHART CLAMP BODY EA 1 0 36 400006 0071 SET SCREW 5 40 X 5 16 EA 1 0 37 512610 COVER W LOGO EA 1 0 38 524743 CHART KNOB EA 1 0 3...

Страница 20: ...that pen arm transport tie down is removed from unit Increase damping See IOM page 10 Ok Now CONTACT FACTORY Will pen arm move with input now CONTACT FACTORY YES GO TO NEXT PAGE Do pen arm display ag...

Страница 21: ...Loop Check chart rotation speed chart knob tightness power outages motor backlash Chart turn ok CONTACT FACTORY Chart turn ok YES NO Fast Slow Not at all NO YES YES 3000 should be operating properly...

Страница 22: ...CULAR PURPOSE Eastech Badger shall not be liable for any defects attributable to acts or omissions of others after shipment nor any consequential incidental or contingent damage whatsoever NUCLEAR DIS...

Отзывы: