There are two blank alarms for future use which are
represented by the dashed lines. Press the UP or DOWN
arrow keys to select the desired alarm and then press the
ENTER key. The second relay assignment will appear
with the same alarm functions to be selected as above.
After assigning the desired alarm the following screen
will appear:
CONTACT INTEGRATOR
0
13
000 X 1,000 GAL
This screen allows the setting of the contact integrator to
the desired amount of totalized flow for each pulse output.
For example, if the desire is to have a contact closure every
10,000 gallons, then the number to be entered is 0010.
Press the UP or DOWN arrow keys to change the value
of the digit and the RIGHT arrow key to move the cursor
under the digit to be changed. Press the ENTER key. The
following screen will appear:
INTEGRATOR PULSE WIDTH
ON FOR 0000 X .0328 SEC.
This screen allows the setting of the pulse width of the
contact integrator output pulse. If the device being
connected to the contact integrator output requires an
input with a pulse width of 50 milliseconds, then the
multiplier would be set to 2. Use the RIGHT arrow key to
move the cursor under the digit to be changed and the UP
or DOWN arrow keys to set the desired value and press
the ENTER key. The following screen will appear:
SET POINT ADJUSTMENT
HI ALARM = 99 PERCENT
This screen allows the setting of the High and Low alarm
set points. Press the UP or DOWN arrow keys to the desired
value and then press the ENTER key. The LO alarm screen
set point will appear. Follow the same procedure above to
set the Low alarm. The following screen will appear:
SETPOINT ADJUSTMENT
HYSTERESIS = 03 PERCENT
This screen sets the hysteresis for the High and Low
alarm set points. If the High alarm is set for 60 percent
and the hysteresis is 3 percent, then the High alarm will
trip closed at 63 percent and open at 57 percent.
Press the UP or DOWN arrow keys to the desired value
and press the ENTER key. The following screen will
appear:
PRESS UP FOR 4-20
CURRENT CALIBRATION
This screen allows the entry into the calibration of the
retransmitted 4-20 mA output. Press the UP arrow key to
enter into the current calibration. The following screen
will appear:
4-20 CURRENT OUT
ZERO WORD=3000
This screen allows the setting for the Zero output of the
4-20 mA current output circuit for 4 mA. Connect a current
meter to the output terminals and monitor the current output.
The Zero word is a four digit word with the digit to the far
left being the coarse adjustment and digits moving to the
right being the finer adjustments. Press the RIGHT arrow
key to move the cursor under the desired digit for
adjustment and press the UP or DOWN arrow keys to adjust
the output to the proper value. Press the ENTER key to store
the new value. The following screen will appear:
4-20 CURRENT OUT
SPAN WORD=A235
This screen allows the setting of the Span output of the 4-
20 mA current output circuit for 20 mA. Connect a current
meter to the output terminals and monitor the current
output. The Span word is a four digit word with the digit to
the far left being coarse adjustment and digits moving to the
right being the finer adjustments. Press the RIGHT arrow
key to move the cursor under the desired digit for
adjustment and press the UP or DOWN arrow keys to
adjust the output to the proper value. Press the ENTER key
to store the new value. The following screen will appear:
SECURITY ID
PRESS UP TO CHANGE
This screen allows the entry into the security code
screen which allows the entry of a new code. Press the
UP arrow key and the following screen will appear:
SECURITY ID
INPUT 4 DIGIT ID 0000