-TOTALIZER WORD-
0
15
000 0000 0000
The Totalizer Word is required to setup the time base to
properly totalizer in the selected option units. The
totalizer word is defined as follows:
HEX
2,000,000
x
ec
in Units/S
Flow
Max.
Multiplier
Totalizer
=
EXAMPLE:
Maximum flow = 1800 x 1 BPM (Barrels/min)
Totalizer multiplier = BAR x 100
Totalizer Word =
[100/(1800/60)] x 2,000,000 = 6666666.6
Converted to Hexadecimal = 65B9AA (see the Decimal
to Hexadecimal Conversion Section).
The TOTALIZER WORD is 0000 0065 B9AA
NOTE: The totalizer word must be greater than Hex
1000.
Use the UP and DOWN arrow keys to change each
digit to the required value and the RIGHT arrow to move
the cursor. The ENTER key must be depressed after each
set of four digits. Return to Page 10 where the next screen
will be the Chart Speed selection.
ERROR SCREENS
There are several Error Screens that will be displayed
by the recorder if the microprocessor detects errors in the
values programmed into the recorder.
-CHART PEN ZERO-
<INPUT ZERO ERROR>
OR
-CHART PEN SPAN-
<INPUT SPAN ERROR>
If either of the two above Error Screens appear during
the chart pen adjusting procedure, one of the following
problems probably occurred:
1. There was not a 4-20 mADC analog signal to the
recorder analog channel you selected while adjusting the
chart zero span.
2. An analog input signal channel was selected
without adjusting the chart pen zero and span of this
channel.
3. The Zero and Span of the recorder have been
adjusted too close to the same input value.
To correct these errors, readjust the Chart Pen Zero and
Span while inputting the 4-20 mADC analog signal to the
proper selected recorder channel. Refer to the Calibration
Mode Section of this manual.
-STORING PARAMETERS-
<TOTALIZER WORD ERROR>
If the above Error Screen appears after pressing the
ENTER key to store the calibration adjustments, this
indicates that you have selected a totalizer multiplier that
is too low for your selected flow rate. To correct this
error, re-enter the Calibration Mode and when the
Totalizer Multiplier Screen appears, increase the totalizer
multiplier and press the ENTER key. Then press the
MENU key to store the new multiplier and return to the
normal operating screen.
If you still have a Totalizer Word Error message in the
Storing Parameters screen, repeat the above procedure
until the error is not present.