5
5
Operation
To optimize water and energy savings, the HXV Hybrid Cooler operates in two modes. In each
mode, capacity is controlled by fan motor modulation, and all of the process fluid flows
through the finned coil (dry coil) and then through the prime surface coil (wet coil).
Operating Modes
(Con’t next page)
•
Energy Saver Mode (Wet Mode)
: The spray water circulating pump distributes water
over the outside of the prime surface coil (wet coil). The spray water falls from the
prime surface coil over the fill surface, where the spray water temperature is further
reduced through evaporation. The cooled spray water collects in the cold water basin,
passes through the suction strainer and is pumped through the distribution system.
The fans draw air through the prime surface coil and through the fill surface (sensible
and latent heat transfer), which saturates the air before it enters the plenum and flows
into the fans. The saturated discharge air from the fans passes over the finned coil (dry
coil) to cool the process fluid (sensible heat transfer). This mode take full advantage of
evaporative cooling, and therefore reduces the fan energy necessary for cooling.
•
Water Saver Mode (Dry Mode):
The process fluid flows through the finned coil (dry coil)
and the prime surface coil. However, the spray water circulating pump is turned off,
which saves pump energy. There is only sensible heat transfer across both coils, as
the air passes over them. This mode is typically used during periods of lower ambient
temperatures or lower heat loads. During prolonged periods of dry mode operation,
draining the cold water basin is recommended, minimizing the need for freeze protection
and water treatment.
Unit Operation and
Storage
Operation
Figure 2a.
Energy Saver Mode
Figure 2b:
Water Saver Mode
Internal Access Ladder
and Platform
NOTE:
Schematic drawings are not
representations of actual units.
Refer to submittal for your specific
configuration.