E8
(10)
1-12-2 Kawana, Fujisawa
Kanagawa 251-8522 Japan
URL
: https://www.azbil.com
Specifications are subject to change without notice.
1st edition: Sep. 2003
23rd edition: Oct. 2018 (V)
Do assignment bank:
dO
Display
Item
Contents
Initial
value
User
level
Ot
1.
1
to
Ot2.
1
Ev
1.
1
to
Ev3.
1
Control output 1 to 2,
event output 1 to 3
Operation type
0: Input of default
1: MV1 (ON/OFF control output, time
proportional output, heat-side proportional
output of heat/cool control)
2: MV2 (cool-side proportional output of heat/
cool control)
3: Function 1 ((A and B) or (C and D))
4: Function 2 ((A or B) and (C or D))
5: Function 3 (A or B or C or D)
6: Function 4 (A and B and C and D)
0
2
Ot
1.2
to
Ot2.2
Ev
1.2
to
Ev3.2
Control output 1 to 2,
event output 1 to 3
Output assignment A
0: Normally open (OFF, 0)
1: Normally close (ON, 1)
2: Internal event 1
3: Internal event 2
4: Internal event 3
5: Internal event 4
6: Internal event 5
7 to 13: Undefined
14: MV1
15: MV2
16, 17: Undefined
18: DI1
19: DI2
20: DI3
21: DI4
22 to 25: Undefined
26: Internal contact 1
27: Internal contact 2
28: Internal contact 3
29: Internal contact 4
30: Internal contact 5
31 to 33: Undefined
34: Communication DI1
35: Communication DI2
36: Communication DI3
37: Communication DI4
38: MANUAL mode
39: READY mode
40: Undefined
41: During AT execution
42: During SP ramp
43: Undefined
44: Alarm is enabled.
45: PV alarm is enabled.
46: Undefined
47: Mode key function selection status
48: Event output 1 status
49: Control output 1 status
14, 15
or
2 to 4
2
Ot
1.3
to
Ot2.3
Ev
1.3
to
Ev3.3
Control output 1 to 2,
event output 1 to 3
Output assignment B
0
2
Ot
1.4
to
Ot2.4
Ev
1.4
to
Ev3.4
Control output 1 to 2,
event output 1 to 3
Output assignment C
0
2
Ot
1.5
to
Ot2.5
Ev
1.5
to
Ev3.5
Control output 1 to 2,
event output 1 to 3
Output assignment D
0
2
Ot
1.6
to
Ot2.6
Ev
1.6
to
Ev3.6
Control output 1 to 2,
event output 1 to 3
Polarity A to D
Digits are called as 1st digit, 2nd digit, 3rd digit
and 4th digit from the right end digit.
0000
2
1st digit: Polarity A
0: Direct
1: Reverse
0
2nd digit: Polarity B
0
3rd digit: Polarity C
0
4th digit: Polarity D
0
Ot
1.7
to
Ot2.7
Ev
1.7
to
Ev3.7
Control output 1 to 2,
event output 1 to 3
Polarity
0: Direct
1: Reverse
0
2
Ot
1.8
to
Ot2.8
Ev
1.8
to
Ev3.8
Control output 1 to 2,
event output 1 to 3 Latch
0: Disabled
1: Enabled (Latch at ON)
2: Enabled (Latch at OFF, except at the time of
initialization after power ON)
0
2
User function bank:
UF
Display
Item
Contents
Initial
value
User
level
UF-
1
User function
definition 1
This is the display in upper display. The setup
exception is as follows:
----
: Yet to be registered.
P-
_ : Proportional band of the PID group in
use
I
-
_ : Integration time of the PID group in
use
d-
_ : Derivative time of the PID group in
use
rE-
_ : Manual reset of the PID group in use
OL-
_ : MV low limit of the PID group in use
OH-
_ : MV high limit of the PID group in use
P-
_
C
: Cool-side proportional band of the
PID group in use
I
-
_
C
: Cool-side integration time of the PID
group in use
d-
_
C
: Cool-side derivative time of the PID
group in use
Ol.
_
C
: Cool-side MV low limit of the PID
group in use
Oh.
_
C
: Cool-side of MV high limit of the PID
group in use
- - - -
1
UF-2
User function
definition 2
- - - -
1
UF-3
User function
definition 3
- - - -
1
UF-4
User function
definition 4
- - - -
1
UF-5
User function
definition 5
- - - -
1
UF-6
User function
definition 6
- - - -
1
UF-7
User function
definition 7
- - - -
1
UF-8
User function
definition 8
- - - -
1
Lock bank:
LOC
Display
Item
Contents
Initial
value
User
level
LOC
Key lock
0: All settings are enabled.
1: Mode, event, operation display, SP, UF, lock,
manual MV, and mode key can be set.
2: Operation display, SP, UF, lock, manual MV,
and mode key can be set.
3: UF, lock, manual MV, and mode key can
be set.
0
0
C.LOC
Communication lock
0: RS-485 communication read/write is
enabled.
1: RS-485 communication read/write is
disabled.
0
2
L.LOC
Loader lock
0: Loader communication read/write is
enabled.
1: Loader communication read/write is
disabled.
0
2
PASS
Password display
0 to 15
5: Password 1A to 2B display
0
0
PS
1A
Password 1A
0000 to FFFF (hexadecimal value)
0000
0
PS2A
Password 2A
0000 to FFFF (hexadecimal value)
0000
0
PS
1b
Password 1B
0000 to FFFF (hexadecimal value)
0000
0
PS2b
Password 2B
0000 to FFFF (hexadecimal value)
0000
0
Instrument information bank:
I
d
Display
Item
Contents
Initial
value
User
level
I
d0
1
ROM ID
1 fixed
—
2
I
d02
ROM version 1
XX. XX (2 digits after decimal point)
—
2
I
d03
ROM version 2
XX. XX (2 digits after decimal point)
—
2
I
d04
SLP support Information
—
2
I
d05
EST support version
—
2
I
d06
Manufacturing date code
(year)
Year −2000
Ex.: “3” means the year 2003.
—
2
I
d07
Manufacturing date code
(month, day)
Month + Day ÷ 100
Ex.: “12.01” means the 1st day of December
—
2
I
d08
Serial No.
—
2