Azbil SDC25 Скачать руководство пользователя страница 15

E7

Display

Item

Contents

Initial 

value

User 

level

C

 

8

 

1

MS indicating lamp  

ON condition  

(1st priority)

0: Normally open (Normally OFF=0)

1: Normally close (Normally ON=1)

2 to 6: Internal event 1 to 5

7 to 9: Internal event 6 to 8 (Invalid in this unit)

10 to 13: Undefined

14:  MV1 (ON/OFF, time proportional 1, heat-side, 

OPEN-side output)

15:  MV2 (time proportional 2, cool-side, CLOSE-side 

output)

16, 17: Undefined

18 to 21: DI1 to DI4

22 to 25: Undefined

26 to 30: Internal contact 1 to 5

31 to 33: Undefined

34 to 37: Communication DI1 to DI4

38: MANUAL

39: READY

40: RSP

41: AT

42: During ramp

43: Undefined

44: Alarm

45: PV alarm

46: Undefined

47: Mode key function selection status

48: Event output 1 status

49: Control output 1 status

39

2

C

 

82

MS indicating lamp ON 

status (1st priority)

0: Lit

1: Slow flashing

2: 2 times flashing

3: Fast flashing

4: Left 

 Right

5: Right 

 Left

6: Right to left going and returning

7: Deviation OK

8: Deviation graph

9: MV graph

10: Heat-side MV graph

11: Cool-side MV graph

12: MFB graph

13: DI monitor

14: Internal contact monitor

15: Internal event monitor

1

2

C

 

83

MS indicating lamp ON 

condition (2nd priority)

Same as MS indicating lamp ON condition (1st 

priority)

44

2

C

 

84

MS indicating lamp ON 

status (2nd priority)

Same as MS indicating lamp ON status (1st priority)

6

2

C

 

85

MS indicating lamp ON 

condition (3rd priority)

Same as MS indicating lamp ON condition (1st 

priority)

1

2

C

 

86

MS indicating lamp ON 

status (3rd priority)

Same as MS indicating lamp ON status (1st priority)

9

2

C

 

87

MS indicating lamp 

deviation range

0 to 9999 U

5

2

C

 

88

Special function

0 to 15 (0 at power supply ON.)

0

2

C

 

89

Zener barrier adjustment Rewriting by adjustment is enabled.

Numerical value inputting manually is disabled

0.00

2

C

 

90

Number of CT1 turns

0: 800 turns

1 to 40:  Setting value multiplied by one hundred 

becomes number of winding.

8

2

C

 

9

 

1

Number of CT1 power 

wire loops

0: 1 time

1 to 6: Number of times

1

2

C

 

92

Number of CT2 turns

0: 800 turns

1 to 40:  Setting value multiplied by one hundred 

becomes number of winding.

8

2

C

 

93

Number of CT2 power 

wire loops

0: 1 time

1 to 6: Number of times

1

2

C

 

97

PV input failure  

(under range) type

0: –10 %FS

1:   –5 mV(This setting is applicable if 

C0

 

1

 (PV input 

range type) is set for sensor type B (No. 17) or 

PR40-20 (No. 23))

0

0

 

„

Event assignment bank: 

EvCF

Display

Item

Contents

Initial 

value

User 

level

E

 

1.C

 

1

 to 

E5.C

 

1

Operation type of 

internal event 1 to 5

Configuration 1

Operation type

0: No event

1: PV high limit

2: PV low limit

3: PV high/low limit

4: Deviation high limit

5: Deviation low limit

6: Deviation high/low limit

7: Deviation high limit (Final SP reference)

8: Deviation low limit (Final SP reference)

9: Deviation high/low limit (Final SP reference)

10: SP high limit

11: SP low limit

12: SP high/low limit

13: MV high limit

14: MV low limit

15: MV high/low limit

16: CT1 heater burnout/over-current

17: CT1 heater short-circuit

18: CT2 heater burnout/over-current

19: CT2 heater short-circuit

20: Loop diagnosis 1

21: Loop diagnosis 2

22: Loop diagnosis 3

23: Alarm (status)

24: READY (status)

25: MANUAL (status)

26: Invalid

27: During AT execution (status)

28: During SP ramp (status)

29: Control direct action (status)

30: Invalid

31: Invalid

32: Timer (status)

33: MFB high/low limit

0

0

Display

Item

Contents

Initial 

value

User 

level

E

 

1.C2

 to 

E5.C2

Internal event 1 to 5

Configuration 2

Digits are called as 1st digit, 2nd digit, 3rd digit 

and 4th digit from the right end digit.

0000

0

1st digit: Direct/Reverse 0: Direct

1: Reverse

0

2nd digit: Stand-by

0: None

1: Standby

2: S Standby at SP change

0

3rd digit: EVENT state 

at READY

0: Continue

1: Forced OFF

0

4th digit: Undefined

0

0

E

 

1.C3

 to 

E5.C3

Internal event 1 to 5

Configuration 3

Digits are called as 1st digit, 2nd digit, 3rd digit 

and 4th digit from the right end digit.

0000

2

1st digit: Alarm OR

0: No event

1: Alarm OR operation

2: Alarm AND operation

3: Alarm r OR operation

4: Alarm r AND operation

0

2nd digit: Special OFF

0: As normal execution

1: Event OFF at the event setting value 

(main)=0

0

3rd digit: Delay time unit 0: 0.1 s

1: 1 s

2: 1 min

0

4th digit: Undefined

0

0

 

„

DI assignment bank: 

dI

Display

Item

Contents

Initial 

value

User 

level

dI

  

1.

 

1

 to 

dI

 

5.

 

1

Internal contact 1 to 5 
Operation type

0: No function
1: LSP group selection (0/+1)
2: LSP group selection (0/+2)
3: LSP group selection (0/+4)
4: PID group selection (0/+1)
5: PID group selection (0/+2)
6: PID group selection (0/+4)
7: RUN/READY selection
8: AUTO/MANUAL selection
9: Invalid
10: AT Stop/Start
11: Invalid
12:  Control action direct/reverse selection (As 

per setting/opposite operation of setting)

13: SP ramp Enabled/Disabled
14: PV Hold (No-hold/Hold)
15: PV maximum value hold (No-hold/Hold)
16: PV minimum value hold (No-hold/Hold)
17: Timer Stop/Start
18: Release of all DO latches (Continue/Release)
19: Invalid
20: Invalid

0

0

dI

  

1.2

 to 

dI

 

5.2

Internal contact 1 to 5 
Input bit operation

0: Disabled. (Input of default)
1: Function 1 ((A and B) or (C and D))
2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)

0

2

dI

  

1.3

 to 

dI

 

5.3

Internal contact 1 to 5 
Input assignment A

0: Normally open (OFF, 0)
1: Normally close (ON, 1)
2: DI1
3: DI2
4: DI3
5: DI4
6 to 9: Undefined
10: Internal event 1
11: Internal event 2
12: Internal event 3
13: Internal event 4
14: Internal event 5
15 to 17: Undefined
18: Communication DI1
19: Communication DI2
20: Communication DI3
21: Communication DI4
22: MANUAL mode
23: READY mode
24: Undefined
25: During AT execution
26: During SP ramp
27: Undefined
28: Alarm is enabled.
29: PV alarm is enabled.
30: Undefined
31: Mode key function selection status
32: Event output 1 status
33: Control output 1 status

2 to 5

or 0

2

dI

  

1.4

 to 

dI

 

5.4

Internal contact 1 to 5 
Input assignment B

0

2

dI

  

1.5

 to 

dI

 

5.5

Internal contact 1 to 5 
Input assignment C

0

2

dI

  

1.6

 to 

dI

 

5.6

Internal contact 1 to 5 
Input assignment D

0

2

dI

  

1.7

 to 

dI

 

5.7

Internal contact 1 to 5 
Polarity A to D

Digits are called as 1st digit, 2nd digit, 3rd digit 
and 4th digit from the right end digit.

0000

2

1st digit: Polarity A 
(Polarity of input 
assignment A)

0: Direct
1: Reverse

0

2nd digit: Polarity B 
(Polarity of input 
assignment B)

0

3rd digit: Polarity C 
(Polarity of input 
assignment C)

0

4th digit: Polarity D 
(Polarity of input 
assignment D)

0

dI

  

1.8

 to 

dI

 

5.8

Internal contact 1 to 5 
Polarity

0: Direct
1: Reverse

0

2

dI

  

1.9

 to 

dI

 

5.9

Internal contact 1 to 5 
Internal event 
No.assignment

0: Every internal event
1 to 5: Internal event numbers

0

2

Содержание SDC25

Страница 1: ...25 26 35 36 SLP C35 CP UM 5290 SDC25 26 CP SP 1217 https www compoclub com SDC25 26 81409654 001 2 CP UM 5288JE 1 mode display enter para man ev1 ev2 ev3 ot1 ot2 sp out pv SDC26 SDC25 man ev1 ev2 ev3...

Страница 2: ...0 5 0 0 5 0 C26 30 30 92 0 5 0 92 0 5 0 0 5 0 96 N 4 92 0 5 0 3 40 AC T 0 5 A 250 V IEC127 M3 50 cm 2 OFF ON OFF 81401325 1 2 RS 485 5 30 7 8 9 CT1 CT2 13 14 15 2 1 2 1 16 17 1 2 1 2 RS 485 22 23 24...

Страница 3: ...800 0 26 0 0K 360 0K No 17 B 260 4 0 FS 260 800 0 4 FS 20 No 23 PR40 20 0 300 2 5 FS 300 800 1 5 FS 800 1900 0 5 FS No 26 2 0 K C0 1 AL0 1 PV PV PV AL02 PV AL03 CJ PV AL 1 1 CT CT 1 2 CT CT CT CT CT...

Страница 4: ...2 100 4000 100 AC 0 4A 800 1 2000 AC 50 0A 800 1 16 AC 70 0 A 800 1 16 1 4 AC 0 0 A AC 70 0 A 800 1 16 1 4 5 FS AC 0 1 A z z 1 NO AC250 V DC30 V 3 A 2 NC AC250 V DC30 V 1 A NO 5 NC 10 5 V 100 mA 250 m...

Страница 5: ...s 0 9999 0 1 s 0 2 E 1 OF E5 OF 1 5 OFF 0 2 0 1 2 PID PI d P 1 P 4 PID1 4 0 1 999 9 5 0 0 I 1 I 4 PID1 4 0 9999 s 0 120 0 d 1 d 4 PID1 4 0 9999 s 0 30 0 rE 1 rE 4 PID1 4 10 0 110 0 50 0 0 OL 1 OL 4 P...

Страница 6: ...0 mA 1 0 C 43 1 0 MV 1 MV 2 MV 3 PV 4 PV 5 SP 6 PV SP 7 CT1 8 CT2 9 MFB C25 26 10 SP MV 11 PV MV 0 0 C 44 1 1999 9999 1 0 0 0 C 45 1 100 0 0 C 46 1 MV 0 9999 1 10 11 200 0 C 47 2 1 1 0 C 48 2 3 0 C 49...

Страница 7: ...26 27 AT 28 SP 29 30 31 32 33 MFB 0 0 E 1 C2 E5 C2 1 5 2 1 2 3 4 0000 0 1 0 1 0 2 0 1 2 SP 0 3 READY 0 1 OFF 0 4 0 0 E 1 C3 E5 C3 1 5 3 1 2 3 4 0000 2 1 OR 0 1 OR 2 AND 3 OR 4 AND 0 2 OFF 0 1 0 OFF 0...

Страница 8: ...t2 3 Ev 1 3 Ev3 3 1 2 1 3 B 0 2 Ot 1 4 Ot2 4 Ev 1 4 Ev3 4 1 2 1 3 C 0 2 Ot 1 5 Ot2 5 Ev 1 5 Ev3 5 1 2 1 3 D 0 2 Ot 1 6 Ot2 6 Ev 1 6 Ev3 6 1 2 1 3 A D 1 2 3 4 0000 2 1 A 0 1 0 2 B 0 3 C 0 4 D 0 Ot 1 7...

Страница 9: ...e SDC25 26 be sure to turn the power OFF Failure to do so might cause electric shock or faulty operation Do not touch electrically charged parts such as the power termi nals Doing so might cause elect...

Страница 10: ...label on the controller side Handling Precautions Before wiring the SDC25 26 verify the controller s model No and terminal Nos written on the label on the side of the body Inspect all wiring once wiri...

Страница 11: ...800 0 C 0 to 1500 F 13 E 0 0 to 600 0 C 0 to 1100 F 14 T 200 0 to 400 0 C 300 to 700 F 15 R 0 to 1600 C 0 to 3000 F 16 S 0 to 1600 C 0 to 3000 F 17 B 0 to 1800 C 0 to 3300 F 18 N 0 to 1300 C 0 to 230...

Страница 12: ...turn units Current measurement lower limit 0 4 A AC 800 turns 1 time Formula Number of turns 2000 number of power wire loops Current measurement upper limit 50 0 A AC 800 turns 1 time Formula Number o...

Страница 13: ...operation type 0 to 9999 for some operation type 0 0 E 1 Sb to E5 Sb Internal event 1 to 5 sub setting 0 0 E 1 Hy to E5 Hy Internal event 1 to 5 hysteresis 0 to 9999 The decimal point position varies...

Страница 14: ...pe 0 0 C 50 Control output 2 scaling high limit 1000 0 Display Item Contents Initial value User level C 5 1 Control output 2 MV scalable bandwidth 0 to 9999 Available when control output 2 type is 10...

Страница 15: ...p status 29 Control direct action status 30 Invalid 31 Invalid 32 Timer status 33 MFB high low limit 0 0 Display Item Contents Initial value User level E 1 C2 to E5 C2 Internal event 1 to 5 Configurat...

Страница 16: ...to 2 event output 1 to 3 Latch 0 Disabled 1 Enabled Latch at ON 2 Enabled Latch at OFF except at the time of initialization after power ON 0 2 User function bank UF Display Item Contents Initial value...

Отзывы: