Azbil SDC25 Скачать руководство пользователя страница 11

E3

 

z

I/O isolation

Items surrounded by solid lines are insulated from other signals.

Availability of input or output is based on a model number.

Power supply

Internal

Circuit

Control output 1

Control output 2

PV input

Current Transformer input 1

Current Transformer input 2

Loader communication

Auxiliary output

Digital input 1

Digital input 2

Digital input 3

Digital input 4

RS-485 Communication

Event output 1*

Event output 2*

Event output 3

*  In case of independent contact, the part between the event 

output 1 and the event output 2 is isolated.

KEY OPERATION AND SETTING

The following shows the flow of key operation:

There are the standard type and special type in the data setup method.

Here, the method is explained in the standard type.

Operation display

Bank selection display

Bank setup display

OFF

OFF

mode

display

enter

para

man

ev1

ev2

ev3

ot1

ot2

sp

out

pv

SDC26

The mode indicators are lit sequentially form 

the left during a period of 5 to 6 sec after the 

power has been turned ON while both the 

upper display and lower display are OFF. 

When all mode indicators have been lit, the 

display is changed to the operation display.

The display and setup status shown above are examples for explanation. Therefore, 

some displays or settings are not shown actually according to the model and/or setup 

contents. After the setup bank  is selected in the Bank selection display, 

C0

 

1

 is shown in 

the Bank setup display.

Display when the power is turned ON.

PV range type setup

Temperature unit setup

Mode bank selection

SP bank selection

Other display and setup

 (Operate the 

[display] key repeatedly.)

PV/SP display

display

key.

Press the

display

key.

Press the

display

key.

Press the

MV display

para

key.

Press the

key.

Press the

para

key.

Press the

key.

Press the

para

key.

Press the

key.

Press the

para

key.

Press the

key.

Press the

para

key.

Press the

key.

Press the

para

key.

Press the

key.

Press the

Other banks

(Operate the [para], [   ]

and [   ] keys repeatedly.)

Other setup

(Operate the [para], [   ]

and [   ] keys repeatedly.)

No key operation for 3 minutes 

or more.

mode

Press the 

or key.

display

No key operation for

3 minutes or more.

enter

Press the
 

or

 key.

Keep the
 key 

pressed 

for 2 sec. 

or longer.

para

mode

Press the 

or key.

display

Keep the
 key 

pressed 

for 2 sec. 

or longer.

para

 

z

Setting example of the PV range type

If the mode bank (

MOdE

) is selected, use the 

[ ] [ ]

 keys to move to 

the setup bank (

StUP

), and then press the 

[enter]

 key. Next, press 

the 

[ ] [ ]

 keys as necessary to display 

C

 

0

 

1

 on the upper display. 

Move the digit or increase/decrease the numeric value by pressing 

the

 [<] [ ] [ ]

 keys. When the 

[enter]

 key is pressed at the desired 

numeric value, the flashing will stop and the data will be set.

 

z

Setting example of the SP1

If the mode bank (

MOdE

) is selected, use the 

[ ] [ ]

 keys to move to 

the setup bank (

SP

), and then press the 

[enter]

 key. Next, press the 

[ ] [ ]

 keys as necessary to display 

SP-

 

1

 on the upper display.

When the 

[enter]

 key is pressed, the numerical value on the lower 

display will start to flash. Move the digit or increase/decrease 

the numeric value by pressing the 

[<] [ ] [ ]

 keys. When the 

[enter]

 key is pressed at the desired numeric value, the flashing 

will stop and the data will be set.

For details of the handling and setting methods, refer to the following 

user’s manual:

  

Single Loop Controller SDC25/26 User’s Manual “Installation & 
Configurations” CP-SP-1149E or SDC25/26 Quick Reference Guide 
CP-SP-1217E.

PV RANGE TABLE

C0

 

1�

set 

value

Input 

type

Range

1

K

−200 to +1200 °C −300 to +2200 °F

2

K

0 to 1200 °C

0 to 2200 °F

3

K

0.0 to 800.0 °C

0 to 1500 °F

4

K

0.0 to 600.0 °C

0 to 1100 °F

5

K

0.0 to 400.0 °C

0 to 700 °F

6

K

−200.0 to +400.0 °C −300 to +700 °F

7

K

−200.0 to +200.0 °C −300 to +400 °F

8

J

0 to 1200 °C

0 to 2200 °F

9

J

0.0 to 800.0 °C

0 to 1500 °F

10

J

0.0 to 600.0 °C

0 to 1100 °F

11

J

−200.0 to +400.0 °C −300 to +700 °F

12

E

0.0 to 800.0 °C

0 to 1500 °F

13

E

0.0 to 600.0 °C

0 to 1100 °F

14

T

−200.0 to +400.0 °C −300 to +700 °F

15

R

0 to 1600 °C

0 to 3000 °F

16

S

0 to 1600 °C

0 to 3000 °F

17

B

0 to 1800 °C

0 to 3300 °F

18

N

0 to 1300 °C

0 to 2300 °F

19

PLII

0 to 1300 °C

0 to 2300 °F

20 Wre5-26

0 to 1400 °C

0 to 2400 °F

21 Wre5-26

0 to 2300 °C

0 to 4200 °F

22 Ni-NiMo

0 to 1300 °C

0 to 2300 °F

23 PR40-20

0 to 1900 °C

0 to 3400 °F

24

DIN U −200.0 to +400.0 °C −300 to +700 °F

25

DIN L −100.0 to +800.0 °C −150 to +1500 °F

26 Gold iron 

chromel

0.0K to 360.0 K

0 to 360 K

 Handling Precautions

• 

The accuracy varies according to 

the range.

• 

The accuracy of the B thermo-

couple is ±4.0 %FS for a range of 

260 °C or less, ±0.4 %FS for 260 to 

800 °C. The PV values under 20 °C 

are not shown. 

The accuracy of the No. 23 (sensor 

type PR40-20) is ±2.5 %FS for 0 to 

300 °C, and ±1.5 %FS for 300 to 

800 °C, ±0.5 %FS for 800 to 1900 °C. 

The accuracy of the No. 26 (sensor type gold iron chromel) is ±2.0 K. 

The accuracy of the No. 19 (sensor type PLII) in the range of 0 to 32 °F does 

not meet the indication accuracy.

• 

The ranges with a decimal point show figures under decimal point.

• 

Make sure to set the correct number in setup display 

C0

 

1

, according to 

the type and range of the sensor used. If the setting is wrong, problems 

such as large temperature errors in the output may occur.

ALARM CODE TABLE

This table shows the alarm display and measures for the abnormal operation 

of this controller.

Alarm 

code

Failure name

Cause

Corrective action

AL0

 

1

PV input failure 

(over range)

Sensor line break, 

incorrect wiring, incorrect 

PV range type setting

Checking wiring or reset 

PV range type.

AL02

PV input failure 

(under range)

AL03

CJ failure

Terminal temperature is 

faulty (thermocouple).

Checking the ambient 

temperature.

PV input failure

Sensor line break, 

incorrect wiring (RTD)

Checking wiring.

AL

 

1

 

1

CT input failure 

(over range) 

(CT input 1 or 2, or both)

A current exceeding the 

upper limit of the display 

range was measured. 
The number of CT turns or 

the number of CT power 

wire loops is incorrectly 

set, or wiring is incorrect.

Use a CT with the correct 

number of turns for the 

display range, reset the 

number of CT turns, reset 

the number of CT power 

wire loops, and/or check 

the wiring.

AL70

A/D conversion failure

Defective A/D converter

Replace unit.

AL95

Parameter failure

Power turned OFF during 

fixing data
Data corrupted due to 

noise, etc.

Re-start the system.
Reset data or replace unit. 

(

AL95

/

97

: setting data, 

AL96

/

98

: tuning data)

AL96

Adjustment data failure

AL97

Parameter failure 

(RAM area)

Data corrupted due to 

noise, etc.

AL98

Adjustment data failure 

(RAM area)

AL99

ROM failure

ROM (memory) error

Re-start the system.
Replace unit.

C0

 

1�

set value

Input type

Range

81

0 to 10 mV

The scaling and 

the decimal point 

position can be 

changed variably 

in a range of −1999 

to +9999.

82

−10 to +10 mV

83

0 to 100 mV

84

0 to 1 V

86

1 to 5 V

87

0 to 5 V

88

0 to 10 V

89

0 to 20 mA

90

4 to 20 mA

C0

 

1�

set 

value

Input 

type

Range

41

Pt100 −200.0 to +500.0 °C −300 to +900 °F

42 JPt100 −200.0 to +500.0 °C −300 to +900 °F
43

Pt100 −200.0 to +200.0 °C −300 to +400 °F

44 JPt100 −200.0 to +200.0 °C −300 to +400 °F
45

Pt100 −100.0 to +300.0 °C −150 to +500 °F

46 JPt100 −100.0 to +300.0 °C −150 to +500 °F
47

Pt100 −100.0 to +200.0 °C −150 to +400 °F

48 JPt100 −100.0 to +200.0 °C −150 to +400 °F
49

Pt100 −100.0 to +150.0 °C −150 to +300 °F

50 JPt100 −100.0 to +150.0 °C −150 to +300 °F
51

Pt100 −50.0 to +200.0 °C −50 to +400 °F

52 JPt100 −50.0 to +200.0 °C −50 to +400 °F
53

Pt100 −50.0 to +100.0 °C −50 to +200 °F

54 JPt100 −50.0 to +100.0 °C −50 to +200 °F
55

Pt100

−60.0 to +40.0 °C −60 to +100 °F

56 JPt100 −60.0 to +40.0 °C −60 to +100 °F
57

Pt100

−40.0 to +60.0 °C −40 to +140 °F

58 JPt100 −40.0 to +60.0 °C −40 to +140 °F
59

Pt100 −10.00 to +60.00 °C −10 to +140 °F

60 JPt100 −10.00 to +60.00 °C −10 to +140 °F
61

Pt100

0.0 to 100.0 °C

0 to 200 °F

62 JPt100

0.0 to 100.0 °C

0 to 200 °F

63

Pt100

0.0 to 200.0 °C

0 to 400 °F

64 JPt100

0.0 to 200.0 °C

0 to 400 °F

65

Pt100

0.0 to 300.0 °C

0 to 500 °F

66 JPt100

0.0 to 300.0 °C

0 to 500 °F

67

Pt100

0.0 to 500.0 °C

0 to 900 °F

68 JPt100

0.0 to 500.0 °C

0 to 900 °F

Содержание SDC25

Страница 1: ...25 26 35 36 SLP C35 CP UM 5290 SDC25 26 CP SP 1217 https www compoclub com SDC25 26 81409654 001 2 CP UM 5288JE 1 mode display enter para man ev1 ev2 ev3 ot1 ot2 sp out pv SDC26 SDC25 man ev1 ev2 ev3...

Страница 2: ...0 5 0 0 5 0 C26 30 30 92 0 5 0 92 0 5 0 0 5 0 96 N 4 92 0 5 0 3 40 AC T 0 5 A 250 V IEC127 M3 50 cm 2 OFF ON OFF 81401325 1 2 RS 485 5 30 7 8 9 CT1 CT2 13 14 15 2 1 2 1 16 17 1 2 1 2 RS 485 22 23 24...

Страница 3: ...800 0 26 0 0K 360 0K No 17 B 260 4 0 FS 260 800 0 4 FS 20 No 23 PR40 20 0 300 2 5 FS 300 800 1 5 FS 800 1900 0 5 FS No 26 2 0 K C0 1 AL0 1 PV PV PV AL02 PV AL03 CJ PV AL 1 1 CT CT 1 2 CT CT CT CT CT...

Страница 4: ...2 100 4000 100 AC 0 4A 800 1 2000 AC 50 0A 800 1 16 AC 70 0 A 800 1 16 1 4 AC 0 0 A AC 70 0 A 800 1 16 1 4 5 FS AC 0 1 A z z 1 NO AC250 V DC30 V 3 A 2 NC AC250 V DC30 V 1 A NO 5 NC 10 5 V 100 mA 250 m...

Страница 5: ...s 0 9999 0 1 s 0 2 E 1 OF E5 OF 1 5 OFF 0 2 0 1 2 PID PI d P 1 P 4 PID1 4 0 1 999 9 5 0 0 I 1 I 4 PID1 4 0 9999 s 0 120 0 d 1 d 4 PID1 4 0 9999 s 0 30 0 rE 1 rE 4 PID1 4 10 0 110 0 50 0 0 OL 1 OL 4 P...

Страница 6: ...0 mA 1 0 C 43 1 0 MV 1 MV 2 MV 3 PV 4 PV 5 SP 6 PV SP 7 CT1 8 CT2 9 MFB C25 26 10 SP MV 11 PV MV 0 0 C 44 1 1999 9999 1 0 0 0 C 45 1 100 0 0 C 46 1 MV 0 9999 1 10 11 200 0 C 47 2 1 1 0 C 48 2 3 0 C 49...

Страница 7: ...26 27 AT 28 SP 29 30 31 32 33 MFB 0 0 E 1 C2 E5 C2 1 5 2 1 2 3 4 0000 0 1 0 1 0 2 0 1 2 SP 0 3 READY 0 1 OFF 0 4 0 0 E 1 C3 E5 C3 1 5 3 1 2 3 4 0000 2 1 OR 0 1 OR 2 AND 3 OR 4 AND 0 2 OFF 0 1 0 OFF 0...

Страница 8: ...t2 3 Ev 1 3 Ev3 3 1 2 1 3 B 0 2 Ot 1 4 Ot2 4 Ev 1 4 Ev3 4 1 2 1 3 C 0 2 Ot 1 5 Ot2 5 Ev 1 5 Ev3 5 1 2 1 3 D 0 2 Ot 1 6 Ot2 6 Ev 1 6 Ev3 6 1 2 1 3 A D 1 2 3 4 0000 2 1 A 0 1 0 2 B 0 3 C 0 4 D 0 Ot 1 7...

Страница 9: ...e SDC25 26 be sure to turn the power OFF Failure to do so might cause electric shock or faulty operation Do not touch electrically charged parts such as the power termi nals Doing so might cause elect...

Страница 10: ...label on the controller side Handling Precautions Before wiring the SDC25 26 verify the controller s model No and terminal Nos written on the label on the side of the body Inspect all wiring once wiri...

Страница 11: ...800 0 C 0 to 1500 F 13 E 0 0 to 600 0 C 0 to 1100 F 14 T 200 0 to 400 0 C 300 to 700 F 15 R 0 to 1600 C 0 to 3000 F 16 S 0 to 1600 C 0 to 3000 F 17 B 0 to 1800 C 0 to 3300 F 18 N 0 to 1300 C 0 to 230...

Страница 12: ...turn units Current measurement lower limit 0 4 A AC 800 turns 1 time Formula Number of turns 2000 number of power wire loops Current measurement upper limit 50 0 A AC 800 turns 1 time Formula Number o...

Страница 13: ...operation type 0 to 9999 for some operation type 0 0 E 1 Sb to E5 Sb Internal event 1 to 5 sub setting 0 0 E 1 Hy to E5 Hy Internal event 1 to 5 hysteresis 0 to 9999 The decimal point position varies...

Страница 14: ...pe 0 0 C 50 Control output 2 scaling high limit 1000 0 Display Item Contents Initial value User level C 5 1 Control output 2 MV scalable bandwidth 0 to 9999 Available when control output 2 type is 10...

Страница 15: ...p status 29 Control direct action status 30 Invalid 31 Invalid 32 Timer status 33 MFB high low limit 0 0 Display Item Contents Initial value User level E 1 C2 to E5 C2 Internal event 1 to 5 Configurat...

Страница 16: ...to 2 event output 1 to 3 Latch 0 Disabled 1 Enabled Latch at ON 2 Enabled Latch at OFF except at the time of initialization after power ON 0 2 User function bank UF Display Item Contents Initial value...

Отзывы: