SDC25/26 LIST OF PARAMETERS

[List of Operation Displays]

 

„

Operation Displays

Display

Item

Contents

Initial 

value

User 

level

Upper 
display: PV
Lower 
display: SP

SP (Target value)

SP low limit (

C07

) to SP high limit (

C08

)

0

0

LSP

 

1

 *

Lower 
display: LSP

LSP No. (1st digit: Value 
at the right end digit)

1 to LSP system group (

C30

 Max. 4)

1

0

Upper 
display: PV
Lower 
display: MV

MV (Manipulated 
Variable)

–10.0 to +110.0 %
Setting is disabled in AUTO mode.
(Numeric value does not flash.)
Setting is enabled in MANUAL mode.
(Numeric value flashes.)

0

HEAt

Heat MV (Manipulated 
Variable)

Setting is disabled
–10.0 to +110.0 %

0

COOL

Cool MV (Manipulated 
Variable)

0

Upper 
display: PV

At

 

1

 *

AT progress display  
(1st digit = Numeric 
value at right end digit)

Setting is disabled.
Except for 0: During execution of AT (Value is 
decreased.)
0: Completion of AT

0

Ct

 

1

CT (Current transformer) 
current value 1

Setting is disabled.

0

Ct2

CT (Current transformer) 
current value 2

Setting is disabled.

0

E

 

1

Internal event 1
main setting

Setting range is different depending on the 
internal event operation type.
–1999 to +9999 U: Except below.
0 to 9999 U: Setting value is an absolute value.
–199.9 to +999.9 %: For MV.

0

0

E

 

1.Sb

Internal event 1  
sub-setting

0

0

t

 

1.--

*

Timer remaining time 1 Setting is disabled.

Upper display: The distinction by ON delay or OFF 
delay is displayed at the side location of “

t

 

1.

”.

Lower display: Displayed by the unit (either 
one of 0.1 s, s, or min) based on the internal 
event 1 delay time unit (

E

 

1

. the 3rd digit of 

C3

).

0

E2

Internal event 2  
main setting

Setting range is different depending on the 
internal event operation type.
–1999 to +9999 U: Except below.
0 to 9999 U: Setting value is an absolute value.
–199.9 to +999.9 %: For MV.

0

0

E2.Sb

Internal event 2  
sub-setting

0

0

t2.--

*

Timer remaining time 2 Setting is disabled.

Upper display: The distinction by ON delay or 
OFF delay is displayed at the side location of “

t2.

”.

Lower display: Displayed by the unit (either 
one of 0.1 s, s, or min) based on the internal 
event 2 delay time unit (

E2

. the 3rd digit of 

C3

).

0

E3

Internal event 3  
main setting

Setting range is different depending on the 
internal event operation type.
–1999 to +9999 U: Except below.
0 to 9999 U: Setting value is an absolute value.
–199.9 to +999.9 %: For MV.

0

0

E3.Sb

Internal event 3  
sub-setting

0

0

t3.--

*

Timer remaining time 3 Setting is disabled.

Upper display: The distinction by ON delay or OFF 
delay is displayed at the side location of “

t3.

”.

Lower display: Displayed by the unit (either 
one of 0.1 s, s, or min) based on the internal 
event 3 delay time unit (

E3

. the 3rd digit of 

C3

).

0

* Display example

[List of Parameter Setting Displays]

 

„

Mode bank: 

MOdE

Display

Item

Contents

Initial 

value

User 

level

A--M

AUTO/MANUAL mode 
selection

AUTO

:  AUTO mode

MAN

:  MANUAL mode

AUTO

0

r--r

RUN/READY mode 
selection

RUN

:  RUN mode

RDY

:  READY mode

RUN

0

At

AT Stop/Start selection

At.OF

:  AT Stop

At.ON

: AT Start

AT Stop 0

dO.Lt

Release all DO latches

Lt.ON

:  Latch continue

Lt.OF

:  Latch release

Latch 

continue

0

C.dI

  

1

Communication DI 1

dI

 

.OF

: OFF

dI

 

.On

: ON

OFF

0

 

„

SP bank: 

SP

Display

Item

Contents

Initial 

value

User 

level

SP-

 

1

 to 

SP-4

SP of LSP1 group to SP 
of LSP4 group

SP low limit (

C07

) to SP high limit (

C08

)

0

0

PI

 

d.

 

1

 to 

PI

 

d.4

PID group No. (for LSP1 
to 4)

1 to 4

1

1

 

„

Event bank: 

Ev

Display

Item

Contents

Initial 

value

User 

level

E

 

1

 to 

E5

Internal event 1 to 5, 
main setting

–1999 to +9999
The decimal point position varies by meeting 
the internal event operation type.
0 to 9999 for some operation type.

0

0

E

 

1.Sb

 to 

E5.Sb

Internal event 1 to 5, 
sub-setting

0

0

E

 

1.Hy

 to 

E5.Hy

Internal event 1 to 5, 
hysteresis

0 to 9999
The decimal point position varies by meeting 
the internal event operation type.

5

0

E

 

1.On

 to 

E5.On

Internal event 1 to 5, 
ON delay

0.0 to 999.9 (For the delay time unit 0.1 s)
0 to 9999 (Except for the delay time unit 0.1 s)

0

2

E

 

1.OF

 to 

E5.OF

Internal event 1 to 5, 
OFF delay

0

2

User level details   0: Display in basic/standard/high function,  

 

1: Display in standard/high function,  

 

2: Display in high function.  

Initial value may vary depending on model No.

 

„

PID bank: 

PI

 

d

Display

Item

Contents

Initial 

value

User 

level

P-

 

1

 to 

P-4

  Proportional band 

(PID1 to 4 group)

0.1 to 999.9 %

5.0

0

I

 

-

 

1

 to 

I

 

-4

  Integration time 

(PID1 to 4 group)

0 to 9999 s or 0.0 to 999.9 s (0: No integral 
control action)

120

0

d-

 

1

 to 

d-4

  Derivative time 

(PID1 to 4 group)

0 to 9999 s or 0.0 to 999.9 s (0: No derivative 
control action)

30

0

rE-

 

1

 to 

rE-4

 

Manual reset 
(PID1 to 4 group)

–10.0 to +110.0 %

50.0

0

OL-

 

1

 to 

OL-4

 

MV low limit 
(PID1 to 4 group)

–10.0 to +110.0 %

0.0

1

OH-

 

1

 to 

OH-4

 

MV high limit 
(PID1 to 4 group)

–10.0 to +110.0 %

100.0

1

P-

 

1C

 to 

P-4C

Cool-side proportional 
band (PID1 to 4 group)

0.1 to 999.9 %

5.0

0

I-

 

1C

 to 

I-4C

Cool-side integration 
time (PID1 to 4 group)

0 to 9999 s or 0.0 to 999.9 s (0: No integral 
control action)

120

0

d-

 

1C

 to 

d-4C

Cool-side derivative 
time (PID1 to 4 group)

0 to 9999 s or 0.0 to 999.9 s (0: No derivative 
control action)

30

0

OL.

 

1C

 to 

OL.4C

Cool-side MV low limit 
(PID1 to 4 group)

–10.0 to +110.0 %

0.0

1

OH.

 

1C

 to 

OH.4C

Cool-side MV high limit 
(PID1 to 4 group)

–10.0 to +110.0 %

100.0

1

 

„

Parameter bank: 

PAra

Display

Item

Contents

Initial 

value

User 

level

CtrL

Control method

0: ON/OFF control
1: PID fixed

0 or 1

0

At.OL

MV low limit at AT

–10.0 to +110.0 %

0.0

0

At.OH

MV high limit at AT

–10.0 to +110.0 %

100.0

0

dI

 

FF

ON/OFF control 
differential

0 to 9999 U

5

0

OFFS

ON/OFF control 
operating point offset

–1999 to 9999 U

0

2

FL

PV filter

0.0 to 120.0 s

0.0

0

rA

PV ratio

0.001 to 9.999

1.000

1

bI

PV bias

–1999 to +9999 U

0

0

CyU

Time proportional cycle 
unit 1

0: 1 s unit
1: 0.5 s fixed (Cycle time is disabled.)
2: 0.25 s fixed (Cycle time is disabled.)
3: 0.1 s fixed (Cycle time is disabled.)

0

2

Cy

Time proportional 
cycle1

5 to 120 s *

1

1 to 120 s *

2

10 or 2

0

CyU2

Time proportional cycle 
unit 2

0: 1 s unit
1: 0.5 s fixed (Cycle time is disabled.)
2: 0.25 s fixed (Cycle time is disabled.)
3: 0.1 s fixed (Cycle time is disabled.)

0

2

Cy2

Time proportional 
cycle 2

5 to 120 s *

1

1 to 120 s *

2

10 or 2

0

tP.ty

Time proportional 
operation type

0: Controllability aiming type
1:  Actuator life aiming type (Only one ON/

OFF operation within time proportional 
cycle time)

0 or 1

2

SPU

SP ramp-up

0.0 to 999.9 U (0.0: No ramp)

0.0

2

SPd

SP ramp-down

0.0

2

*1. When the output includes the relay output.
*2. When the output does not include the relay output.

 

„

Extension tuning bank: 

Et

Display

Item

Contents

Initial 

value

User 

level

At.ty

AT type

0:  Normal (Standard control characteristics)
1:  Immediate response (Control characteristics 

immediately responding to the external 
disturbance.)

2:  Stable (Control characteristics with less up/

down function of PV)

0

0

JF.bd

Just-FiTTER setting band 0.00 to 10.00

0.30

2

SP.LG

SP lag constant

0.0 to 999.9

0.0

2

At-P

AT proportional band 
tuning factor

0.00 to 99.99

1.00

2

At-I

AT integration time 
tuning factor

0.00 to 99.99

1.00

2

At-d

AT derivative time 
tuning factor

0.00 to 99.99

1.00

2

Ctr.A

Control algorithm

0: PID (conventional PID)
1: RationaLOOP (high performance type)

0

1

JF.Ov

Just-FiTTER overshoot 
suppression factor

0 to 100

0

1

Содержание SDC25

Страница 1: ...25 26 35 36 SLP C35 CP UM 5290 SDC25 26 CP SP 1217 https www compoclub com SDC25 26 81409654 001 2 CP UM 5288JE 1 mode display enter para man ev1 ev2 ev3 ot1 ot2 sp out pv SDC26 SDC25 man ev1 ev2 ev3...

Страница 2: ...0 5 0 0 5 0 C26 30 30 92 0 5 0 92 0 5 0 0 5 0 96 N 4 92 0 5 0 3 40 AC T 0 5 A 250 V IEC127 M3 50 cm 2 OFF ON OFF 81401325 1 2 RS 485 5 30 7 8 9 CT1 CT2 13 14 15 2 1 2 1 16 17 1 2 1 2 RS 485 22 23 24...

Страница 3: ...800 0 26 0 0K 360 0K No 17 B 260 4 0 FS 260 800 0 4 FS 20 No 23 PR40 20 0 300 2 5 FS 300 800 1 5 FS 800 1900 0 5 FS No 26 2 0 K C0 1 AL0 1 PV PV PV AL02 PV AL03 CJ PV AL 1 1 CT CT 1 2 CT CT CT CT CT...

Страница 4: ...2 100 4000 100 AC 0 4A 800 1 2000 AC 50 0A 800 1 16 AC 70 0 A 800 1 16 1 4 AC 0 0 A AC 70 0 A 800 1 16 1 4 5 FS AC 0 1 A z z 1 NO AC250 V DC30 V 3 A 2 NC AC250 V DC30 V 1 A NO 5 NC 10 5 V 100 mA 250 m...

Страница 5: ...s 0 9999 0 1 s 0 2 E 1 OF E5 OF 1 5 OFF 0 2 0 1 2 PID PI d P 1 P 4 PID1 4 0 1 999 9 5 0 0 I 1 I 4 PID1 4 0 9999 s 0 120 0 d 1 d 4 PID1 4 0 9999 s 0 30 0 rE 1 rE 4 PID1 4 10 0 110 0 50 0 0 OL 1 OL 4 P...

Страница 6: ...0 mA 1 0 C 43 1 0 MV 1 MV 2 MV 3 PV 4 PV 5 SP 6 PV SP 7 CT1 8 CT2 9 MFB C25 26 10 SP MV 11 PV MV 0 0 C 44 1 1999 9999 1 0 0 0 C 45 1 100 0 0 C 46 1 MV 0 9999 1 10 11 200 0 C 47 2 1 1 0 C 48 2 3 0 C 49...

Страница 7: ...26 27 AT 28 SP 29 30 31 32 33 MFB 0 0 E 1 C2 E5 C2 1 5 2 1 2 3 4 0000 0 1 0 1 0 2 0 1 2 SP 0 3 READY 0 1 OFF 0 4 0 0 E 1 C3 E5 C3 1 5 3 1 2 3 4 0000 2 1 OR 0 1 OR 2 AND 3 OR 4 AND 0 2 OFF 0 1 0 OFF 0...

Страница 8: ...t2 3 Ev 1 3 Ev3 3 1 2 1 3 B 0 2 Ot 1 4 Ot2 4 Ev 1 4 Ev3 4 1 2 1 3 C 0 2 Ot 1 5 Ot2 5 Ev 1 5 Ev3 5 1 2 1 3 D 0 2 Ot 1 6 Ot2 6 Ev 1 6 Ev3 6 1 2 1 3 A D 1 2 3 4 0000 2 1 A 0 1 0 2 B 0 3 C 0 4 D 0 Ot 1 7...

Страница 9: ...e SDC25 26 be sure to turn the power OFF Failure to do so might cause electric shock or faulty operation Do not touch electrically charged parts such as the power termi nals Doing so might cause elect...

Страница 10: ...label on the controller side Handling Precautions Before wiring the SDC25 26 verify the controller s model No and terminal Nos written on the label on the side of the body Inspect all wiring once wiri...

Страница 11: ...800 0 C 0 to 1500 F 13 E 0 0 to 600 0 C 0 to 1100 F 14 T 200 0 to 400 0 C 300 to 700 F 15 R 0 to 1600 C 0 to 3000 F 16 S 0 to 1600 C 0 to 3000 F 17 B 0 to 1800 C 0 to 3300 F 18 N 0 to 1300 C 0 to 230...

Страница 12: ...turn units Current measurement lower limit 0 4 A AC 800 turns 1 time Formula Number of turns 2000 number of power wire loops Current measurement upper limit 50 0 A AC 800 turns 1 time Formula Number o...

Страница 13: ...operation type 0 to 9999 for some operation type 0 0 E 1 Sb to E5 Sb Internal event 1 to 5 sub setting 0 0 E 1 Hy to E5 Hy Internal event 1 to 5 hysteresis 0 to 9999 The decimal point position varies...

Страница 14: ...pe 0 0 C 50 Control output 2 scaling high limit 1000 0 Display Item Contents Initial value User level C 5 1 Control output 2 MV scalable bandwidth 0 to 9999 Available when control output 2 type is 10...

Страница 15: ...p status 29 Control direct action status 30 Invalid 31 Invalid 32 Timer status 33 MFB high low limit 0 0 Display Item Contents Initial value User level E 1 C2 to E5 C2 Internal event 1 to 5 Configurat...

Страница 16: ...to 2 event output 1 to 3 Latch 0 Disabled 1 Enabled Latch at ON 2 Enabled Latch at OFF except at the time of initialization after power ON 0 2 User function bank UF Display Item Contents Initial value...

Отзывы: