background image

AB-6208-U 

Installation location 

 CAUTION 

 

Do not install the product nearby a steam coil, pressurized hot-water coil, or any high heat source. High temperature 
radiation might cause malfunction of its actuator. 

 

Do not use the product in an atmosphere corrosive to the actuator, valve, and their components. Doing so might
damage the product. 

 

  Install the valve assembled with the actuator in a position allowing easy access for maintenance and inspection. Fig. 1 

shows the minimum clearance for maintenance and inspection. When installing the valve and actuator in a ceiling space, 
provide an access panel within the 20” (50 cm) radius of the valve and actuator. And, place a drain pan under the valve. 

  Do not mount the valve on a pipe where water hammer occurs, or where solid objects including slug may accumulate. 

 

Mounting position 

The valve (assembled with the actuator) can be mounted in any position ranging from upright to sideways (90

 tilted). The valve 

should be installed with its actuator vertically positioned above the valve body. However, the valve must be installed always in 
upright position outdoors. 

 

 

 

 

 

 

Figure 4.   Mounting positions of the valve 

 

Piping 

  Install a bypass pipe and gate valves on the inflow, outflow, and bypass sides. Also, install a strainer (with 40 or more 

meshes) on the inflow side. 

  When installing the valve to pipes, do not allow any object, such as chips, to get inside a pipe or valve. Valve cannot fully 

closes, or the valve seat may get damaged causing fluid leakage, due to an foreign object jammed inside the valve. 

  When piping, do not apply too much sealing material, such as solidifying liquid and tape, to the pipe connection sections so 

that these materials flow into the valve. Valve cannot fully closes, or the valve seat may get damaged causing fluid leakage, 
due to the sealing material jammed inside the valve. 

  When connecting the valve to pipes, hold the valve body (where a pipe is screwed) with a tool such as a wrench, and screw 

the pipe into the valve. (See Fig. 5.)  Do not apply excessive torque to the pipe. Refer to the table in Fig. 5 for the 
recommended torque.  

 

 

 

 

 

 

 

 

 

Figure 5.  Valve connection to a pipe 

 

  Before activating the valve and actuator, flush the pipes (with the valve and actuator installed) at the maximum flow rate to 

remove all the foreign substances. Fully open (in 100 % position) the valve to flush. (Factory preset position: 100 %) 

 

 

Correct examples 

 

 

 

 

   Incorrect examples 

 

Recommended torque to screw into the pipe 

Valve size 

1/2”

3/4” 

1” 

1

1

/

4

1

1

/

2

Max. torque 

in-lbs (N

m) 

360 

(40)

540 

(60) 

890 

(100) 

1070 

(120)

1340 

(150)

Incorrect

holding position

Correct holding 
position 

Torque 

Содержание ACTIVAL VY5302B

Страница 1: ...ed space such as inside of a compact AHU Bronze valve body applicable to 230 psig Easy assembly with Model MY53X0A actuator using no tool and no adjustment required Equal percentage flow characteristic AHU Air handling unit This product was designed and manufactured conforming to the ISO International Organization for Standardization PN16 Model Numbers Base model number Material Size Cv Descriptio...

Страница 2: ...tmosphere etc listed in the specifications Failure to do so might cause fire or device failure Use the product within its lifespan and avoid instrumentations that keep the product to operate excessively Continued use beyond the lifespan might cause fire or device failure Keep the products in package for storage Failure to do so might damage or stain the products Installation and wiring must be per...

Страница 3: ...Valve size Cv close off rating Model number Nominal size Cv Close off rating Inch DN VY5302B0011 1 2 15 2 5 145 psig VY5302B0012 1 2 15 4 145 psig VY5302B0022 3 4 20 6 3 145 psig VY5302B0023 1 25 10 145 psig VY5302B0031 1 1 4 32 16 72 psig VY5302B0041 1 1 2 40 25 72 psig VY5302B0042 1 1 2 40 40 72 psig Materials Body Cast bronze Cap Cast bronze Seat ring Carbon Reinforced PTFE Ball Cast stainless ...

Страница 4: ...ons Doing so might damage the product Do not excessively screw a pipe into the valve Doing so might damage or deform the inside of the valve causing leakage and malfunction Install the product so that no foreign objects remains inside the pipes Be sure to provide a strainer on the inflow side of the piping Flush the piping to remove the foreign objects after installation Foreign objects inside the...

Страница 5: ...the inflow outflow and bypass sides Also install a strainer with 40 or more meshes on the inflow side When installing the valve to pipes do not allow any object such as chips to get inside a pipe or valve Valve cannot fully closes or the valve seat may get damaged causing fluid leakage due to an foreign object jammed inside the valve When piping do not apply too much sealing material such as solid...

Страница 6: ...ositions of the actuator and the valve as follows referring to Fig 7 Actuator Indicator manual lever points at 100 fully open position Valve An arrow on the top of the stem points at 100 fully open position Align the hole on the side of the stem with the tip at the joint surface as a in Fig 7 shows Set the ACTIVAL actuator and valve in 100 position when changing the mounting position If the valve ...

Страница 7: ... direction at which the tip of the valve joint surface with the actuator points when the valve position is fully open See a in Fig 7 Figure 10 Valve stem pointing at 100 fully open position 4 Assemble Model MY53X0A actuator with the valve Engage 4 pins of the actuator with the mating holes on the valve joint surface 5 Move the lock lever to left end to lock Locked position is indicated with the gr...

Страница 8: ...ps halfway valve does not operate at all Conditions of the power applied and of the input signal applied to the actuator Wiring condition disconnected wires of the actuator Foreign substance jammed Check the power supply and the controller connected to Check the wiring Remove foreign substance by manually opening the valve Fluid leaks to the outside of the valve when the assembled actuator fully c...

Отзывы: