background image

AB-6208-U 

Safety Instructions 

Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual nearby for quick 
reference.  

Usage Restrictions 

This product is targeted for general air conditioning. Do not use this product in a situation where human life might be affected.
Also, do not install this product in an atmosphere containing explosive gas or flammable gas. 
If this product is used in a clean room or a place where particularly high reliability or control accuracy is required, please contact
our sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators. 

 

Warnings and Cautions 

 WARNING

 

Alerts users that improper handling may cause death or serious injury. 

 CAUTION

 

Alerts users that improper handling may cause minor injury or material loss. 

 

Signs 

 

Alerts users possible hazardous conditions caused by erroneous operation or erroneous use. The symbol inside I 
indicates the specific type of danger.  
(For example, the sign on the left warns of the risk of electric shock.) 

 

Notifies users that specific actions are prohibited to prevent possible danger. The symbol inside Q graphically 
indicates the prohibited action.  
(For example, the sign on the left notifies that disassembly is prohibited.)  

 

Instructs users to carry out a specific obligatory action to prevent possible danger. The symbol inside d graphically 
indicates the actual action to be carried out.  
(For example, the sign on the left indicates general instructions.) 

 

 CAUTION 

 

Install and use this product under the operating conditions (for temperature, humidity, power, vibration, shock,
mounting direction, atmosphere, etc.) listed in the specifications. Failure to do so might cause fire or device failure. 

 

Use the product within its lifespan and avoid instrumentations that keep the product to operate excessively. 
Continued use beyond the lifespan might cause fire or device failure. 

 

Keep the products in package for storage. Failure to do so might damage or stain the products. 

 

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

 

For installation, do not mount the valve in an improper position or overtighten the threaded connections. 
Doing so might damage the product. 

 

After installation, make sure no fluid leaks from the valve-pipe connections.  
Incorrect installation might cause fluid leakage. 

 

Install the product so that no foreign objects remains inside the pipes. Be sure to provide a strainer on the inflow side
of the piping. Flush the piping to remove the foreign objects after installation. Foreign objects inside the piping might
damage the product. 

 

Do not excessively screw a pipe into the valve. Doing so might damage or deform the inside of the valve causing 
leakage and malfunction. 

 

Do not allow the fluid to freeze. Doing so might damage the valve body and cause fluid leakage. 

 

Do not install the product nearby a steam coil, pressurized hot-water coil, or any high heat source. High temperature 
radiation might cause malfunction of its actuator. 

 

Do not use the product in an atmosphere corrosive to the actuator, valve, and their components. Doing so might
damage the product. 

 

Do not disassemble the product. Doing so might cause device failure. 

 

Do not carelessly touch this product when being used to control hot water. The product temperature is hot, and you 
might get burned. 

 

Dispose of the product as industrial waste in accordance with your local regulations. Do not reuse all or part of this 
product. 

Содержание ACTIVAL VY5302B

Страница 1: ...ed space such as inside of a compact AHU Bronze valve body applicable to 230 psig Easy assembly with Model MY53X0A actuator using no tool and no adjustment required Equal percentage flow characteristic AHU Air handling unit This product was designed and manufactured conforming to the ISO International Organization for Standardization PN16 Model Numbers Base model number Material Size Cv Descriptio...

Страница 2: ...tmosphere etc listed in the specifications Failure to do so might cause fire or device failure Use the product within its lifespan and avoid instrumentations that keep the product to operate excessively Continued use beyond the lifespan might cause fire or device failure Keep the products in package for storage Failure to do so might damage or stain the products Installation and wiring must be per...

Страница 3: ...Valve size Cv close off rating Model number Nominal size Cv Close off rating Inch DN VY5302B0011 1 2 15 2 5 145 psig VY5302B0012 1 2 15 4 145 psig VY5302B0022 3 4 20 6 3 145 psig VY5302B0023 1 25 10 145 psig VY5302B0031 1 1 4 32 16 72 psig VY5302B0041 1 1 2 40 25 72 psig VY5302B0042 1 1 2 40 40 72 psig Materials Body Cast bronze Cap Cast bronze Seat ring Carbon Reinforced PTFE Ball Cast stainless ...

Страница 4: ...ons Doing so might damage the product Do not excessively screw a pipe into the valve Doing so might damage or deform the inside of the valve causing leakage and malfunction Install the product so that no foreign objects remains inside the pipes Be sure to provide a strainer on the inflow side of the piping Flush the piping to remove the foreign objects after installation Foreign objects inside the...

Страница 5: ...the inflow outflow and bypass sides Also install a strainer with 40 or more meshes on the inflow side When installing the valve to pipes do not allow any object such as chips to get inside a pipe or valve Valve cannot fully closes or the valve seat may get damaged causing fluid leakage due to an foreign object jammed inside the valve When piping do not apply too much sealing material such as solid...

Страница 6: ...ositions of the actuator and the valve as follows referring to Fig 7 Actuator Indicator manual lever points at 100 fully open position Valve An arrow on the top of the stem points at 100 fully open position Align the hole on the side of the stem with the tip at the joint surface as a in Fig 7 shows Set the ACTIVAL actuator and valve in 100 position when changing the mounting position If the valve ...

Страница 7: ... direction at which the tip of the valve joint surface with the actuator points when the valve position is fully open See a in Fig 7 Figure 10 Valve stem pointing at 100 fully open position 4 Assemble Model MY53X0A actuator with the valve Engage 4 pins of the actuator with the mating holes on the valve joint surface 5 Move the lock lever to left end to lock Locked position is indicated with the gr...

Страница 8: ...ps halfway valve does not operate at all Conditions of the power applied and of the input signal applied to the actuator Wiring condition disconnected wires of the actuator Foreign substance jammed Check the power supply and the controller connected to Check the wiring Remove foreign substance by manually opening the valve Fluid leaks to the outside of the valve when the assembled actuator fully c...