28
AXOR Industries
Service Manual
MiniMagnum
TM
ver.1 rev.05/'15
2.13 Digital inputs connection
DiGital iNPutS connection
DGT- IN RTN
I/O GND
DGT-IN1
(ENABLE)
+24VDC
refered to I/O GND
CN
MiniMagnum
TM
M1
8
9
10
11
12
DGT-IN2
DGT-IN3
DGT-IN4
10k
DGT-IN RTN
5V1
DGND
Note
:
• The enable signal should be +
24vdc-7ma
(PLC compatible). The enable range is between
+14v
min
and
+30v max
.
• The
m1-8
terminal (
dgT-iN1 (eNaBle)
) is used only as the drive’s enable. If M1-8 is HIGH
(+24VDC) the drive is enabled (without active alarms and if start up sequence, illustrated on para-
graph 2.21, is respected); if M1-8 is LOW (0V), the motor is without torque.
ATTENTION: THE DRIVE'S ENABLE/DISABLE, BY USING THE ENABLE INPUT, IS NOT CONSIDERED A
SECURITY FUNCTION.
• The
m1-9
,
m1-10
,
m1-11
programmable
inputs can be used to activate pre-programmed functions
of the drive (for example: limit switch , electromechanical brake, homing and positioning procedures,
emergency stop, etc.).
For a detailed description of the pre-programmed functions see enclosure "
Speeder One
interface
",
"
additional features
manual
" and "
Positioner
manual
" on the CD provided with the drive.
If there is the
m3
connector (OPTIONAL), it provides five additional digital inputs and one of them is
programmable (M3-7).
• Connect pin
m1-12
(
dgT-iN RTN
) to the ground bar of the system.