The power up of the
minimagnum
TM
must be done following this diagram, in order to save the drive
and the electrical box:
2.22 MiniMagnum
TM
power up
attention:
If the DGT-IN1 (ENABLE)
digital input is enabled by the CN before
powering the drive (A), after powering the
drive utilising the auxiliary supply and the
main supply, it is necessary disable and
enable the DGT-IN1 input (B), in order to
enable the INTERNAL ENABLE. If the DGT-
IN1 is not disabled , then re-enabled, the
INTERNAL ENABLE remains disabled and
the user cannot execute any movement.
1) Power the drive utilising the
auxiliary supply,
+24vdc
.
2) After
1sec.
power the main
supply.
3) the "Relè Ok " contact
closes
(*)
.
4) After
100ms
it is possible
to enable the drive utilising
the "Enable" key or the DGT-
IN1 digital input.
T
T
T
T
AUXILIARY
SUPPLY
MAIN
SUPPLY
RELE' OK
DGT-IN1
(HARDWARE ENABLE)
+24V
+24V
0V
0V
1
0
ON
OFF
1s
50ms
100ms
(1)
(2)
(3)
(4)
T
T
T
+24V
+24V
0V
0V
ON
OFF
1s
DGT-IN1
(HARDWARE ENABLE)
(A)
(B)
T
INTERNAL ENABLE
ON
OFF
AUXILIARY
SUPPLY
MAIN
SUPPLY
attention:
If the digital input DGT-
IN1 (ENABLE) is enabled by the CN
after powering the drive utilising the
auxiliary supply, but before powering the
drive utilising the main supply (C), it is
necessary to disable and then re-enable
DGT-IN1 input (D), in order to enable
the INTERNAL ENABLE also. If the DGT-
IN1 is not disabled then re-enabled, the
INTERNAL ENABLE remains disabled and
the user cannot execute any movement.
T
T
T
MAIN
SUPPLY
+24V
+24V
0V
0V
ON
OFF
AUXILIARY
SUPPLY
DGT-IN1
(HARDWARE ENABLE)
(C)
(D)
T
INTERNAL ENABLE
ON
OFF
(
*
)
It is possible to close the contact after auxiliary supply insertion, setting the "Closed when
ready" function in the "General Settings" window of the
Speeder One
interface.