![AXIOMATIC AXTC4CO Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/axiomatic/axtc4co/axtc4co_user-manual_3037100059.webp)
UMAXTC20CO V1.1.1 Preliminary Documentation – May be Subject to Change A-1
APPENDIX A – Technical Specifications
Inputs
Power Supply Input
12V or 24Vdc nominal (9…36Vdc power supply range)
NB. The maximum total power consumption is <1.5 Watts.
Supply Current
150 mA at 12 V Typical; 90 mA at 24 V Typical
Protection
Reverse polarity protection is provided.
Power supply input section protects against transient surges and shorts.
Isolation
Three way isolation is provided for the CAN line, inputs and power supply.
Isolation voltage is 1500 Vac (rms) or 2550V for 1 sec. for all channels to
power and 50V (rms) for all channels to CAN interface.
Thermocouple Types
Up to 4 channels, independently configurable for J, K or T type sensors.
Thermocouple Inputs
Accuracy: +/- 1°C, Resolution: 0.001°C
Scan Rate
200ms per channel, read simultaneously. 5 scans/second/channel.
Common Mode Readings
Input range +/- 4V maximum
Rejection is 100db at 5Vp-p (50-60Hz)
Thermal Drift
50 ppm/°C of span (maximum)
Averaging
Available on Bank 1 (TC1 and TC2), Bank 2 (TC3 and TC4) and Total (All)
Protection
Open circuit detection
Over or under temperature detection
High temperature shutdown detection
Communication
CAN
1 CAN 2.0Bport, protocol CiA CANopen ®
By default, the Thermocouple Scanner transmits the process value (object
$7130) according to the device profile in CiA Standard DS-404
Network Termination
According to the CAN standard, it is necessary to terminate the network
with external termination resistors. The resistors are 120 Ohm, 0.25W
minimum, metal film or similar type. They should be placed between
CAN_H and CAN_L terminals at both ends of the network.
RS-232
1 RS-232 port available, ASCII Text Format, 115200 Baud Rate
Data – 8 bit, Parity – None, Stop – 1 bit. Flow Control – Xon/Xoff.
Short circuit protection to ground.
General Specifications
Microprocessor
16-bit, 128 KByte flash program memory
Control Logic
User programmable functionality using SDO object access, per CiA DS-301
User Interface
.EDS provided to interface to standard CANopen ® tools
Operating Conditions
-40 to 85
C (-40 to 185
F)
Storage
-50 to 120
C (-58 to 248
F)
Enclosure and
Dimensions
Encapsulated in a rugged aluminum housing 146x149x73mm
(5.75x5.866x2.874”) with watertight Deutsch connectors
Can be mounted directly on the power generator set or remotely
Protection
IP67; Unit is conformal coated within housing.
Vibration
MIL-STD-202G, Test 204D and 214A (Sine and Random)
10 g peak (Sine)
7.68 Grms peak (Random)
Shock
MIL-STD-202G, Test 213B: 50 g
Weight
0.55 lb., 0.25kg