![AXIOMATIC AXTC4CO Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/axiomatic/axtc4co/axtc4co_user-manual_3037100042.webp)
UMAXTC20CO V1.1.1 Preliminary Documentation – May be Subject to Change 42-59
3.4.2.
Object 2010h: Thermocouple Microvolts
This read-only object is available for diagnostic purposes. It reflects the raw microvolt reading
measured by the ADC chip directly.
Object Description
Index 2010h
Name Thermocouple
Microvolts
Object Type
ARRAY
Data Type
INTEGER32
Entry Description
Sub-Index 0h
Description Largest
sub-index supported
Access RO
PDO Mapping
No
Value Range
4
Default Value
4
Sub-Index
1h to 4h (X = 1 to 4)
Description
Thermocouple X Microvolt Reading
Access RO
PDO Mapping
No
Value Range
Dependent on Sensor Type
Default Value
No
3.4.3.
Object 2100h: Average Input Field Value
This read-only object reflects the calculated average of a given subset of thermocouple inputs.
Channels with invalid input data (i.e. disabled or open circuited) are not used in the average
calculations. The average input field values are calculated by adding the temperature of all valid
channels, then dividing by the number of valid inputs.
Object Description
Index 2100h
Name
Average Input Field Value
Object Type
ARRAY
Data Type
FLOAT32
Entry Description
Sub-Index 0h
Description Largest
sub-index supported
Access RO
PDO Mapping
No
Value Range
3
Default Value
3