UMAXTC20CO V1.1.1 Preliminary Documentation – May be Subject to Change 15-59
3. CANOPEN ® OBJECT DICTIONARY
The CANopen object dictionary of the Thermocouple Scanner is based on CiA device profile DS-
404 V1.2 (device profile for Thermocouple Scanners). The object dictionary includes
Communication Objects beyond the minimum requirements in the profile, as well as several
manufacturer-specific objects for extended functionality.
3.1.
NODE ID and BAUDRATE
By default, the Thermocouple Scanner ships factory programmed with a Node ID = 127 (0x7F) and
with Baudrate = 125 kbps.
3.1.1. LSS Protocol to Update
The only means by which the Node-ID and Baudrate can be changed is to use Layer Settling
Services (LSS) and protocols as defined by CANopen ® standard DS-305.
Follow the steps below to configure either variable using LSS protocol. If required, please refer to
the standard for more detailed information about how to use the protocol.
3.1.1.1. Setting
Node-ID
Set the module state to LSS-configuration by
sending
the following message:
Item Value
COB-ID 0x7E5
Length 2
Data 0
0x04
(cs=4 for switch state global)
Data 1
0x01
(switches to configuration state)
Set the Node-ID by
sending
the following message:
Item Value
COB-ID 0x7E5
Length 2
Data 0
0x11
(cs=17 for configure node-id)
Data 1
Node-ID (set new Node-ID as a hexadecimal number)
The module will send the following response (any other response is a failure):
Item Value
COB-ID 0x7E4
Length 3
Data 0
0x11
(cs=17 for configure node-id)
Data 1
0x00
Data 2
0x00