UMAXTC20CO V1.1.1 Preliminary Documentation – May be Subject to Change 13-59
NOISE – ELECTRICAL CONNECTIONS
To reduce noise, separate all thermocouple wires from power wires. Shielded thermocouple wires
will protect against ignition and injector noise.
GROUNDING
To improve the scanners immunity to EMI noise, the Frame GND pin on the grey receptacle should
be connected to a chassis ground. All chassis grounding should go to a single ground point
designated for the engine and all related equipment.
The ground strap that provides a low impedance path for EMI should be a ½ inch wide, flat, hollow
braid, no more than 12 inches long with a suitable sized ring lug for the module’s grounding lug.
SHIELDING
The thermocouple and CAN wiring should be shielded using a twisted conductor pair. All
thermocouple wire shields should be terminated to the associated Shield GND pin on the black
connector. The thermocouple wires should not be exposed for more than 50 m (2 inches) without
shielding. The shield may be cut off at the thermocouple end as it does not require termination at
that end.
Shields can be AC grounded at one end and hard grounded at the opposite end to improve
shielding effectiveness.
If the module is installed in a cabinet, shielded wiring can be terminated at the cabinet (earth
ground), at the entry to the cabinet or at the Thermocouple Scanner.
INPUT POWER
The main input to the power supply must be of low-impedance type for proper operation. If
batteries are used, an alternator or other battery-charging device is necessary to maintain a stable
supply voltage.
Central suppression of any surge events should be provided at the system level.
The installation of the equipment must include overcurrent protection between the power source
and the Thermocouple Scanner by means of a series connection of properly rated fuses or circuit
breakers. Input power switches must be arranged external to the Thermocouple Scanner.
The power input wiring should be limited to 10 meters.
Note the operating temperature range. All field wiring must be suitable for that temperature range.
THERMOCOUPLE INPUT WIRING
Wiring for the thermocouple input must be shielded cable, 16 or 18 AWG. Cable lengths should be
less than 30 meters. Shielding should be unbroken.