3.4.14. Object 4020h: High Temperature Shutdown Threshold
This object sets the high threshold of the shutdown operating temperature range for each
thermocouple’s input field value ($6100.) Any FV value above this limit flags a high shutdown in
the corresponding thermocouple’s status byte ($6150), as well as setting an EMCY code in the
pre-defined error field ($1003). The data in sub-indexes 1 to 4 is interpreted with a fixed resolution
of 0.1°C/bit.
Object Description
Index 4020h
Name
High Temperature Shutdown Threshold
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index 0h
Description Largest
sub-index supported
Access RO
PDO Mapping
No
Value Range
4
Default Value
4
Sub-Index
1h to 4h (X = 1 to 4)
Description
Thermocouple X High Shutdown Temp.
Access RW
PDO Mapping
No
Value Range
(TC X High Warning Temp + 100) to
17350
Default Value
2500 [250°C]
3.4.15. Object 4030h: Error React Delay
This object defines the length of time during which a thermocouple’s input field value must remain
outside of the operating ranges as defined in objects $4000, $4010, and $4020. Should the
temperature go back within the acceptable range during this period, the fault will not be flagged in
the status byte ($6150), nor will an EMCY code be generated in the pre-defined error field ($1003).
Object Description
Index 4030h
Name
Error React Delay
Object Type
ARRAY
Data Type
UNSIGNED16
Entry Description
Sub-Index 0h
Description Largest
sub-index supported
Access RO
PDO Mapping
No
Value Range
4
Default Value
4