Reliable Earthing: Reliable earthing of rack mounted equipment should be maintained. Pay
particular attention to supply connections other than direct connections to the branch circuit
(for example, use of power strips).
Cabling Installation, Maintenance and Safety Tips
The following is a list of important safety considerations that should be reviewed prior to installing
or maintaining your cables:
•
Maintain the twists of the pairs all the way to the point of termination, or no more that one-half
inch untwisted. Do not cut off more than one inch of jacket while terminating.
•
If bending the cable is necessary, make it gradual with no bend sharper than a one inch radius.
Allowing the cable to be sharply bent or kinked can permanently damage the cable’s interior.
•
Dress the cables neatly with cable ties, using low to moderate pressure. Do not over
tighten ties.
•
Cross-connect cables where necessary, using rated punch blocks, patch panels and
components. Do not splice or bridge cable at any point.
•
Keep CAT 5 cable as far away as possible from potential sources of EMI, such as electrical
cables, transformers and light fixtures. Do not tie cables to electrical conduits or lay cables on
electrical fixtures.
•
Always test every installed segment with a cable tester. “Toning” alone is not an
acceptable test.
•
Always install jacks so as to prevent dust and other contaminants from settling on the contacts.
The contacts of the jack should face up on the flush mounted plates, or left/right/down on
surface mount boxes.
•
Always leave extra slack on the cables, neatly coiled in the ceiling or nearest concealed
location. Leave at least five feet at the work outlet side and 10 feet at the patch panel side.
•
Choose either 568A or 568B wiring standard before beginning. Wire all jacks and patch panels
for the same wiring scheme. Do not mix 568A and 568B wiring in the same installation.
•
Always obey all local and national fire and building codes. Be sure to firestop all cables that
penetrate a firewall. Use plenum rated cable where it is required.
HMX Manager Configuration
A typical HMX Manager configuration includes the appliance and the IQs and user stations
connected to the local area network (LAN). A terminal, or a workstation running a terminal
emulation program, is connected to the serial port for configuring basic network settings. The
HMX Manager, IQs and user stations, and user accounts are then configured from the browser
interface to the HMX Manager.
Содержание HMX Manager
Страница 1: ...Installer User Guide HMX Manager ...
Страница 8: ...vi HMX Manager Installer User Guide ...
Страница 30: ...22 HMX Manager Installer User Guide ...
Страница 38: ...30 HMX Manager Installer User Guide ...
Страница 42: ...34 HMX Manager Installer User Guide ...
Страница 46: ...38 HMX Manager Installer User Guide ...
Страница 50: ...42 HMX Manager Installer User Guide ...
Страница 54: ...46 HMX Manager Installer User Guide ...
Страница 55: ......
Страница 56: ...For Technical Support www avocent com support 590 820 501A ...