FXT 5000 Series Installation Guide
3.2.3 AC Mains Disconnect
• The AC power cords serve as AC mains disconnect for the FXT 5000 Series node and therefore must remain
readily accessible during the lifetime of the installation.
• The FXT 5000 Series node is provided with multiple power cords, and has a power-on/standby type power
switch. This switch does not function as an AC mains disconnect. To disconnect all power for maintenance or
an electrical emergency, remove all power cords.
3.2.4 Power Supply Replacement
The power supply units for FXT 5000 Series nodes have detachable power cords. Disconnect the power cord at the
power supply unit before removing it from the node. When installing a power supply unit, insert the unit into the
node before connecting the power cord.
When running on a single power supply unit, the node has an increased probability of losing all power as a result of
the single unit failing. Always replace a failed power supply unit as soon as possible after failure.
3.2.5 Hazardous Energy Levels
• To avoid potential injury, remove all chains, rings, watches, and other metal jewelry before performing
maintenance on powered-on equipment. Burns and other injuries can be caused by the flow of current through
a metallic object if the metallic object comes in contact with powered circuits.
• When replacing externally accessible components while power is applied to the node, never reach into the
empty space created by the removed components, because hazardous energy levels may be present.
3.3 Racked FXT Series Nodes
To avoid the potential of serious injury and equipment damage, observe the following precautions before installing
nodes into racks or before removing them from racks:
• Ensure that the node’s weight is fully supported by two people at all times while it is being installed into or
removed from a rack.
• The rack installation must be designed to remain stable while supporting the full weight of the installed
equipment in its maximum extended position.
3.3. Racked FXT Series Nodes
11
Содержание FXT 5000 Series
Страница 2: ......
Страница 24: ...FXT 5000 Series Installation Guide 20 Chapter 4 Installing an FXT 5000 Series Edge Filer Node in a Rack ...
Страница 32: ...FXT 5000 Series Installation Guide 28 Chapter 5 Making Network Connections to the FXT 5000 Series Node ...
Страница 40: ...FXT 5000 Series Installation Guide 36 Chapter 7 Monitoring the FXT 5000 Series Edge Filer ...
Страница 43: ...CHAPTER NINE EU DECLARATION OF CONFORMITY 39 ...
Страница 44: ...FXT 5000 Series Installation Guide 40 Chapter 9 EU Declaration of Conformity ...