FXT 5000 Series Installation Guide
2.2.4 FXT 5400 Power and Thermal Measurements
FXT 5400 power at room temperature or at maximum fan speed
FXT 5400
At 22° C (71.6° F) Inlet Temperature
At Maximum Fan Speeds
Voltage (V)
100
120
208
230
240
100
120
208
230
240
Frequency (Hz)
60
60
60
50
50
60
60
60
50
50
Current (A)
2.48
2.06
1.22
1.11
1.06
3.21
2.67
1.56
1.40
1.35
Apparent Power (VA)
248
248
255
255
254
321
320
324
322
324
Power Factor
0.99
0.99
0.94
0.93
0.93
0.99
0.99
0.96
0.96
0.95
Real Power (W)
246
245
240
237
236
318
317
312
309
308
Thermal Dissipation
(BTU/Hr)
839
837
817
809
805
1084
1082
1063
1055
1050
2.2.5 FXT 5200 Power and Thermal Measurements
FXT 5200 power at room temperature or at maximum fan speed
FXT 5200
At 22° C (71.6° F) Inlet Temperature
At Maximum Fan Speeds
Voltage (V)
100
120
208
230
240
100
120
208
230
240
Frequency (Hz)
60
60
60
50
50
60
60
60
50
50
Current (A)
2.52
2.09
1.24
1.15
1.10
3.21
2.70
1.59
1.43
1.37
Apparent Power (VA)
252
251
258
265
264
321
324
331
329
329
Power Factor
0.99
0.99
0.94
0.93
0.93
0.99
0.99
0.96
0.96
0.95
Real Power (W)
249
248
242
246
246
318
321
317
316
312
Thermal Dissipation
(BTU/Hr)
851
847
827
839
838
1084
1094
1083
1077
1066
2.2. Power and Thermal Specifications
5
Содержание FXT 5000 Series
Страница 2: ......
Страница 24: ...FXT 5000 Series Installation Guide 20 Chapter 4 Installing an FXT 5000 Series Edge Filer Node in a Rack ...
Страница 32: ...FXT 5000 Series Installation Guide 28 Chapter 5 Making Network Connections to the FXT 5000 Series Node ...
Страница 40: ...FXT 5000 Series Installation Guide 36 Chapter 7 Monitoring the FXT 5000 Series Edge Filer ...
Страница 43: ...CHAPTER NINE EU DECLARATION OF CONFORMITY 39 ...
Страница 44: ...FXT 5000 Series Installation Guide 40 Chapter 9 EU Declaration of Conformity ...