Avaya Model 6000 UPS Operator’s Manual
S
167-405-115 Issue 5
Uncontrolled Copy
Communications Mode Reference Chart
The following chart defines the UPS serial port contacts. Serial
communication is not available with 3Com and AS/400 network
configurations. Use only the applicable pins for the selected
communication mode; otherwise, interference problems may occur.
Communication Mode Function
Signal Name Pin No.
True Condition
Serial
Data to UPS
RS232 TxD
2
N/A
Data from UPS
RS232 RxD
3
N/A
Signal Ground
7
Novell
Battery On
ON.AC
14/16
Open
Low Battery
TWO.MIN
23/24
Closed
Signal Ground
7/15/25
Novell
Battery On
ON.AC
14/16
Closed
Low Battery
TWO.MIN
23/24
Closed
Signal Ground
7/15/25
3Com
Shutdown (Remote)
SHUT.DOWN
2
Positive Voltage
Low Battery
LOW.BATT
9
Positive Voltage
Battery On
PWR.FAIL
10
Positive Voltage
Signal Ground
7
AS/400
(A
D f l )
UPS Available
UPS Available
11/13
Closed
(Avaya Default)
Battery On
Utility Failure
14/16
Closed
Bypass
UPS Offline
17/19
Closed
Low Battery
Low Battery
23/24
Closed
Signal Ground
12/15/18/25
N
N
N
NO
O
O
OT
T
T
TE
E
E
E
Pin numbers separated by a forward slash ( / ) are connected together internally.
Содержание 4500 VA
Страница 6: ...UPS with BDM Quick Installation 5 6 7 8 9 ...
Страница 58: ...UPS Operation 50 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...
Страница 68: ...Communication 60 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...
Страница 74: ...Specifications 66 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...
Страница 83: ......
Страница 84: ...164201342 A 164201342A ...