Installation
38
Avaya Model 6000 UPS Operator’s Manual
S
167-405-115 Issue 5
Uncontrolled Copy
8.
Switch the circuit breaker to the ON (
|
) position (see Figure 4
on page 28) on each battery module connected to the PPU.
Each battery module performs a self-test and then enters
normal operation. The battery module startup should take
about three seconds.
9.
For plug/receptacle units, verify that the circuit protectors for
output receptacles are in the ON position (pushed in).
10.
Switch the PPU input breaker to the ON (
|
) position (see
Figure 4 on page 28).
11.
Switch the BDM input breaker to the ON (
|
) position (see
Figure 5 on page 29).
The UPS performs diagnostic tests and enters Normal mode
with the equipment (load) offline. The
µ
indicator remains
lit. The startup should take about 15 seconds.
12.
Press and hold the Output On button until you hear the UPS
beep (approximately one second).
The
µ
indicator remains lit and the Self Test indicator turns
on. The front panel displays the percentage of full load being
applied to the UPS. The UPS is now in Normal mode with the
load online. See “Normal Mode” on page 42 for more
information.
13.
If you connected a REPO switch to the UPS, test the switch
while the UPS is operating to ensure proper operation.
Press the REPO switch. The UPS shuts down and stops
providing power to the equipment. To restart the UPS, follow
the startup procedure beginning on page 37.
NOTE
If the REPO test fails and the UPS does not shutdown, contact your service
representative.
Содержание 4500 VA
Страница 6: ...UPS with BDM Quick Installation 5 6 7 8 9 ...
Страница 58: ...UPS Operation 50 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...
Страница 68: ...Communication 60 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...
Страница 74: ...Specifications 66 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...
Страница 83: ......
Страница 84: ...164201342 A 164201342A ...