Installation
29
Avaya Model 6000 UPS Operator’s Manual
S
167-405-115 Issue 5
Uncontrolled Copy
NOTE
All battery cords are the same length. See Figure 5 and Figure 7 on for BDM
rear panels.
Utility Input To
BDM (Cord Provided)
Input Breaker
Bypass Switch
5-15R
Receptacles
L5-30R or L14-30R
Receptacles
(Model Dependent)
5-15R Circuit
Protectors
Power Cords
To PPU
Circuit Protectors for
Locking Receptacles
(Model Dependent)
BDM Input Voltage
Selector Switch
Figure 5. BDM Plug/Receptacle Unit Rear Panel Connections
9.
Select the correct UPS output voltage according to the BDM
model:
BDM Model Number
UPS Voltage Selector
Switch Position*
208: 120/240 Hardwired
Set to 208V for 120/240V BDM output
Set to 220V for 127/220V BDM
output (60-Hz units only)
208/240: 120 L5-30R
208 or 240
208/240: 120/240 L14-30R
208 or 240
240: 120/240 Hardwired
240
240: 120/240E Hardwired
Set to 200V for 100/200V BDM output
Set to 220V for 110/220V BDM output
Set to 230V for 115/230V BDM output
Set to 240V for 120/240V BDM output
*The UPS output voltage must match input voltage.