61
Avaya Model 6000 UPS Operator’s Manual
S
167-405-115 Issue 5
Uncontrolled Copy
C H A P T E R
6
S
PECIFICATIONS
Model 6000 Specifications
The following model specifications assume:
S
88% efficiency at full load (Normal mode)
S
Input power factor of 0.95
S
84% efficiency running on battery
Model 5000/6000 UPS (Nominal Operating Specifications)
Output VA
Output
Voltage
Output
Watts
Input Current
Output Current
Normal
(BTUs/hr)
On Battery
(BTUs/hr)
5000
200
3350
19.6A
25.0A
< 1600
< 2200
5200
208
3500
19.7A
25.0A
< 1600
< 2300
5500
220
3700
19.7A
25.0A
< 1700
< 2400
5750
230
3850
19.6A
25.0A
< 1800
< 2500
6000
240
4000
19.5A
25.0A
< 1900
< 2600
Model 5000/6000 UPS with BDM (Nominal Operating Specifications)
Output VA
(PPU)
Output Voltage
(PPU)
Output Watts
Normal (BTUs/hr)
On Battery
(BTUs/hr)
5000
200
3050
< 2600
< 3200
5200
208
3200
< 2600
< 3300
5500
220
3400
< 2700
< 3400
5750
230
3550
< 2800
< 3500
6000
240
3700
< 2900
< 3600
Содержание 4500 VA
Страница 6: ...UPS with BDM Quick Installation 5 6 7 8 9 ...
Страница 58: ...UPS Operation 50 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...
Страница 68: ...Communication 60 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...
Страница 74: ...Specifications 66 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...
Страница 83: ......
Страница 84: ...164201342 A 164201342A ...