R32
Split Type - Air Source Heat Pump 20220105
50
Multiple row installation spacing requirements
Modelname
Amm
B1mm
B2mm
Cmm
ACHP-H04/4R3HA-O
3000 2000 300 600
ACHP-H06/4R3HA-O
ACHP-H08/4R3HA-O
ACHP-H10/4R3HA-O
ACHP-H12/5R3HA-O / ACSHC-H42A5/ASR2DI
ACHP-H14/5R3HA-O / ACSHC-H48A5/ASR2DI
ACHP-H16/5R3HA-O / ACSHC-H60A5/ASR2DI
1.4 Hydronic box
1.4.1 Placement Considerations
Hydronic box should be installed in positions that are as close as possible to the heat emitters.
Hydronic box should be installed in positions that are sufficiently close to the desired position of the wired
controller that the controllers wiring length limitation will not be exceeded.
In systems that are configured to heat domestic hot water, hydronic box should be installed in positions that
are sufficiently close to the domestic hot water tank that the temperature sensor wiring length limitations will not
be exceeded. .
1.4.2 Mounting the hydronic box
1
、
Fix the wall mounting bracket to the wall using appropriate plugs and screws.
Wall bracket
Hydronic box backside
2
、
Make sure the wall mounting bracket is completely level. When the unit is not installed level, air might get
trapped in the water circuit resulting in malfunctioning of the unit. Pay special attention to this when installing
the hydronic box to prevent overflow of the drain pan.
3
、
Hang the hydronic box on the wall mounting bracket
4
、
Fix the hydronic box at the bottom inside using appropriate plugs and screws. The hydronic box is equipped
with 2 holes at the bottom outer edges of the frame.
Содержание ACHP-H04/4R3HA
Страница 23: ...R32 Split Air to Water Heat Pump 20220105 23 2 Hydronic Box AHM P24R2 C9D3A AHM P36R25 C9D9A AHM P60R25 C9D9A ...
Страница 43: ...R32 Split Type Air Source Heat Pump 20220105 43 ...
Страница 94: ...R32 Split Type Air Source Heat Pump 20220105 94 ...
Страница 97: ...R32 Split Type Air Source Heat Pump 20220105 97 Interface Interface setting Loading interface ...