R32
Split Type - Air Source Heat Pump 20220105
46
Strong wind installation direction
1.3.3 Cold ClimateI nstallation
In cold climate locations installation should take account of the following considerations:
Never install the unit at a site where the suction side may be exposed directly to wind.
To prevent exposure to wind, install a baffle plate on the air discharge side of the unit.
To prevent exposure to wind, install the unit with its suction side facing the wall.
In areas of heavy snowfall, a canopy should be installed to prevent snow entering the unit. Additionally, the
height of the base structure should be increased so as to raise the unit further off the ground.
Snow shielding
1.3.4 Hot Climate Installation
As the outdoor temperature is measured via the out door ambient temperature sensor,make sure to install
the outdoor unit in the shade,or a canopy should be constructed to avoid direct sunlight. So that it is not
influenced by the sunsheat,otherwise system protection may occur.
1.3.5 Base Structure
Outdoor unit base structure design should take account of the following considerations:
A solid base prevent sexcess vibration and noise.Outdoor unit bases should be constructed on solid ground
or on structures of sufficien tstrength to support the units weight.
Bases should be at least 100mm high to provide sufficient drainage and to prevent water ingress into the
base of the unit.
Either steel or concrete bases may be suitable.
Outdoor units should no tbe installed on supporting structures that could be damaged by water building in
the event of a blocked drain.
Содержание ACHP-H04/4R3HA
Страница 23: ...R32 Split Air to Water Heat Pump 20220105 23 2 Hydronic Box AHM P24R2 C9D3A AHM P36R25 C9D9A AHM P60R25 C9D9A ...
Страница 43: ...R32 Split Type Air Source Heat Pump 20220105 43 ...
Страница 94: ...R32 Split Type Air Source Heat Pump 20220105 94 ...
Страница 97: ...R32 Split Type Air Source Heat Pump 20220105 97 Interface Interface setting Loading interface ...