14
3
Battery low
The module has
determined that battery
voltage at heater
startup or during heater
operation is lower than
specified in the settings
4.1 or 4.2
Charge car’s battery with
special charger (or start engine
to charge) or cancel 4.1/4.2
module’s settings
4
Time limits
exceeded
Time limit for
autonomous operation
of the heater is
achieved (with active
setting 2.1)
Run the engine or cancel 2.1
module’s setting
5
Unsuccessful
start
The heater was
switched off
spontaneously at
startup
Make diagnostics of the heater
if the error occurs again
6
Operation
cycle too
short
The heater was
switched off
spontaneously with
operating time less
than 20 minutes
Make diagnostics of the heater
if the error occurs again
8
CAN-bus
error
There is a problem
with connection of the
module to the CAN-
bus
Check the connection
9
Settings error Settings have been
incorrectly stored in
RCP memory
Reset the settings (8.1.1),
readjust RCP
11
Heater no
connection
The heater is
unplugged from CAN-
bus or is out of order
Make diagnostics of the heater