Page 7
IronHorse GSDA-DP-S User Manual – 1st Edition – 09/18/2019
P3 t
erMinal
b
lOck
h
OOk
-U
P
D
iaGraM
AC INPUT
AC INPUT
P3-1
P3-2
P3-3
P3-4
P3-5
P3-6
P3-7
P3-8
GSDA-DP-S
2 AMP
P3-9
P3-10
P3-11
P3-12
}
85-265VAC
N
L
+5V
COM
IN2
IN1
4-20 OUT (+)
4-20 OUT (-)
V-OUT (+)
V-OUT (-)
SIGNAL IN (+)
SIGNAL IN (-)
+V_USER
-V_USER
+24VDC SUPPLY
-24VDC SUPPLY
}
OUTPUT TO USER DEVICE
JP5
JP4
JP3
JP1
P3 t
erMinal
b
lOck
D
escriPtiOns
Terminal Block Descriptions
Terminal
Description
P3-1
(AC / N) – For single phase AC lines connect the Neutral side of your AC line to
this terminal� For systems with two hot AC lines, connect either of the Hot AC
lines to this terminal�
P3-2
(AC / L) – For single phase AC lines connect the Hot side of your AC line to this
terminal� For systems with two hot AC lines, connect either of the Hot AC lines to
this terminal�
P3-3
(-SIGNAL IN) – In Scaled Mode, connects to Negative or Common of voltage or
current signal to be attenuated�
P3-4
(+SIGNAL IN) – In Scaled Mode, connects to Positive of voltage or current signal
to be attenuated�
P3-5
(-24VDC SUPPLY) – A 24VDC supply output is provided to the user for sensor or
other device�
P3-6
(+24VDC SUPPLY) – A 24VDC supply output is provided to the user for sensor or
other device�
P3-7
(-mA OUTPUT) – The negative connection for either Scaled or Generated mA
current output signal�
P3-8
(+mA OUTPUT) – The Positive connection for either Scaled or Generated mA
current output signal�
P3-9
IN1 - Contact input for user configurable actions such as specified output, and
set point lock�
P3-10
IN2 - Contact input for user configurable actions such as specified output, and
set point lock�
P3-11
COM
P3-12
+5V