Page 13

IronHorse GSDA-DP-S User Manual –  1st Edition – 09/18/2019

Item

Parameter Name

Description

16

Keypad Scroll Delay

This parameter sets the scroll speed for the front-panel push 

buttons�  The function of this parameter varies slightly depending 

on the Keypad Mode�  See parameter 15 for more details�

18

Power-Up Mode

This parameter defines the mode which determines the default 

Running Value when power is initially applied to the GSDA-DP-S�  

•  Mode 1: Default to Zero 

When in this mode, the unit will default to zero (display units)�

•  Mode 2: Default to Power-Up Value 

When in this mode, the unit will default to the Power-up Value, 

parameter 19�

•  Mode 3: Default to Previously Running Value 

When in this mode, the unit will default to the previous running 

value before power was removed�  A previous running value 

must have been active for at least 3 seconds to be recalled after 

power has been disconnected and reapplied�  

19

Power-Up Value

When Power-up Mode is set to 2, this parameter will designate the 

default display value at power-up in display units�

Display and Output Setup

20

Display Value at Minimum Output

This parameter defines the lower end of the display range�  This 

is the value which limits how low the user is able to scroll the 

displayed value in Running Mode�  This parameter is set without 

consideration for the decimal point’s position�  For example, 

setting this parameter to 125 would set the lower display limit 

at 12�5, 0�125, or 125 according to the other configuration 

parameters�

21

Display Value at Maximum Output

This parameter defines the upper end of the display range�  This 

is the value which limits how high the user is able to scroll the 

displayed value in Running Mode�  This parameter is set without 

consideration for the decimal point’s position�  For example, 

setting this parameter to 1000 would set the upper display limit 

at 100�0, 1�000, or 1000 according to the other configuration 

parameters�

25

Output % - Minimum

(in 1/10 percent units)

This parameter sets the output percentage which corresponds to 

the minimum display value, parameter 20�  This parameter has 

a range of 0 to 1000 which represents 0�0 to +100�0 percent of 

output�  When the user is adjusting the display value towards the 

programmed minimum display, the output will linearly approach 

the value of this parameter�  For example, setting this parameter 

to 25 will configure the GSDA-DP-S to output 2�5% when the user 

adjusts the display value to equal the display minimum, parameter 

20�  See parameters 20 - 22 and the application examples for 

additional information�

26

Output % - Maximum

(in 1/10 percent units)

This parameter sets the output percentage which corresponds to 

the maximum display value, parameter 21�  This parameter has 

a range of 0 to 1000 which represents 0�0 to +100�0 percent of 

output�  When the user is adjusting the display value towards the 

programmed maximum display, the output will linearly approach 

the value of this parameter�  For example, setting this parameter to 

850 will configure the GSDA-DP-S to output 85�0% when the user 

adjusts the display value to equal the display maximum, parameter 

21�  See parameters 20 - 21and the application examples for 

additional information�

Содержание IronHorse GSDA-DP-S

Страница 1: ...Page 1 IronHorse GSDA DP S User Manual 1st Edition 09 18 2019 GSDA DP S Signal Conditioner Generator User Manual User Manual Number GSDA DP S_UMP ...

Страница 2: ...onments requiring fail safe performance such as in the operation of nuclear facilities aircraft navigation or communication systems air traffic control direct life support machines or weapons systems in which the failure of the product could lead directly to death personal injury or severe physical or environmental damage High Risk Activities AutomationDirect specifically disclaims any expressed o...

Страница 3: ... 09 18 2019 Contents Warning 2 Trademarks 2 Publication History 2 GSDA DP S User Manual Overview 4 IronHorse GSDA DP S General Information 4 GSDA DP S Installation 6 GSDA DP S Operation 8 Device Configuration 9 Software Parameters 11 Troubleshooting 16 ...

Страница 4: ...n in the left hand margin the paragraph to its immediate right will be a special note WARNING When you see the exclamation mark icon in the left hand margin the paragraph to its immediate right will be a WARNING This information could prevent injury loss of property or even death in extreme cases IronHorse GSDA DP S General Information The GSDA DP S is a panel mounted multi purpose signal conditio...

Страница 5: ...essly excluded NOTE Carefully check the GSDA DP S for shipping damage Report any damage to the carrier immediately Do not attempt to install the device if visible damage is evident to either the circuit or to the electronic components Specifications GSDA DP S Specifications Electrical Line Input Voltage 85 265 VAC Line Input Frequency 48 62 Hz Voltage Signal Input 0 10 VDC Voltage Signal Output Mi...

Страница 6: ...CONTROL HOUSING APPROXIMATELY 3 622 WIDE BY 1 770 HIGH GSDA DP S CONTROL SUPPLIED WITH EACH CONTROL 1 GASKET 2 2 6 32 X 3 4 PANHEAD BLACK OXIDE STAINLESS SCREWS 3 2 6 NUT WITH LOCKWASHER Exploded Panel View Cut out and Mounting Dimensions HOUSING DEPTH 4 625 117 5 PANEL CUT OUT GSDA DP S x 2 GEN SCL SPL ENTER SIGNAL SCALER AND GENERATOR 4 00 101 6 3 62 91 9 0 885 22 5 1 77 45 0 140 3 6 4 00 101 6 ...

Страница 7: ...his terminal For systems with two hot AC lines connect either of the Hot AC lines to this terminal P3 3 SIGNAL IN In Scaled Mode connects to Negative or Common of voltage or current signal to be attenuated P3 4 SIGNAL IN In Scaled Mode connects to Positive of voltage or current signal to be attenuated P3 5 24VDC SUPPLY A 24VDC supply output is provided to the user for sensor or other device P3 6 2...

Страница 8: ...e only the display setting effects the 4 20mA current output level In voltage output mode the display setting and the maximum level set by the potentiometer R9 adjustment determine the voltage output level see Device Configuration for proper hardware and software setup SPL The GSDA DP S is in Set Point Lock this effectively disables any changes until IN1 IN2 input levels change according to the fu...

Страница 9: ...ed value is showing in the display window pressing the Enter button again will return to Parameter Mode The new value is not saved in permanent memory until the Enter button is pressed Removing power from the unit while in Value Mode may result in the specified new value being lost The front panel Annunciators will be perform as follows Parameter 10 1 Gen annunciator lit Parameter 10 2 SCL annunci...

Страница 10: ... 2 0 10 VDC Input Scaled 4 20 mA or 0 1 20VDC Output 3 No Input Generator 4 20 mA or 0 1 20VDC Output NOTE Both JP3 and JP4 must be set the same GSDA DP S Current Voltage I O Jumpers and Parameter 10 Settings Input Output Parameter 10 JP1 JP3 JP4 JP5 Scale Generate V I In V I Out Reference V I Out Power Supply Application Configuration Pin to Pin Jumper Configuration Current Voltage Scale li Vo Vo...

Страница 11: ...ult to Zero Display 2 Default to Power up Value 3 Default to Previous Running Value 3 19 Power Up Value 0 9999 Eng Units 0 Display and Output Setup Parameters 20 Display Value at Minimum Output 9999 9999 Eng Units 0 21 Display Value at Maximum Output 9999 9999 Eng Units 1000 25 Output Minimum 0 1000 1 10 0 26 Output Maximum 0 1000 1 10 1000 Input 1 IN1 Setup Parameters 30 IN1 Input Configuration 1...

Страница 12: ...example with a Display Zero Blanking setting of 3 and a displayed value of 6 the display would show _006 Mode 1 ___X Always show at least 1 digit Mode 2 __XX Always show at least 2 digits Mode 3 _XXX Always show at least 3 digits Mode 4 XXXX Always show all 4 digits 13 Decimal Point Position This selects the format of the display with respect to the decimal point s position This parameter does not...

Страница 13: ...parameters 21 Display Value at Maximum Output This parameter defines the upper end of the display range This is the value which limits how high the user is able to scroll the displayed value in Running Mode This parameter is set without consideration for the decimal point s position For example setting this parameter to 1000 would set the upper display limit at 100 0 1 000 or 1000 according to the...

Страница 14: ...esponds to the programmed jog setpoint parameter 31 Once the IN1 input returns to an electrically low state or wired to the unit s common the output will once again correspond to the display value Mode 5 Output 100 When IN1 Low When the IN1 input is at an electrically low state or wired to the unit s common the GSDA DP S will force its output to 100 Once the IN1 input returns to an electrically hi...

Страница 15: ...will once again correspond to the display value Mode 5 Output 100 When IN2 Low When the IN2 input is at an electrically low state or wired to the unit s common the GSDA DP S will force its output to 100 Once the IN2 input returns to an electrically high 5V state or allowed to float disconnected the output will once again correspond to the display value Mode 6 Output 100 When IN2 High When the IN2 ...

Страница 16: ...r additional help and instructions Display is dim Display intensity parameter is too low Increase the display intensity parameter to cause the display digits to become brighter S1 or S2 displayed Switch S1 or S2 is active Remove S1 or S2 input Refer to Parameter 30 and 35 for information on settings LOC displayed Parameter 30 or 35 is set to 7 Change input state of S1 or S2 or reprogram Parameter ...

Отзывы: