Page 51
IronHorse GSD8 DC Drives User Manual – 1st Ed. Rev. A – 10/15/2019
ENTER
153.0
Pump Specs:
19 Shaft Rotations = 2 Liters
Pump
Fluid
Outlet
Fluid
Inlet
Audible
Annunciator
GSD8-240-5C
Motor Control
Flow Transducer
(73 Pulses per Liter)
DC Motor
Wiring Diagram
P1-1
P1-2
P1-3
P1-4
P1-5
P1-6
P1-7
P1-8
GSD8-240-5C
*FUSE
MOTOR
P1-9
P1-10
P1-11
P1-12
* Size fuse according to unit and application. See
electrical specifications for maximums.
A+
COM
+5V
S1
S2
NO
C
NC
IN1
N
L
A-
}
AC Line Input 85-265VAC, 50-60 Hz
NOT USED
NOT USED
GND
+V
SIGNAL OUT
FLOW TRANSDUCER
(Frequency Output)
NOT USED
240VAC
Audible
Annunciator
Parameter Configuration:
Parameter
Value
Notes
10
1
Master, Rate Mode Setting (LPM is a rate-based unit)
13
3
Decimal point position set to XXX.X on display
30
10
Display should indiciate 1.0 LPM (10) when pickup at Reference RPM, parameter 31
31
73
This is the RPM at which the Display Reference, parameter 30, should be displayed
32
1
Pulses per revolution of shaft encoder or pickup is 1 PPR
50
7
Alarm active when pickup stalled
53
1
Flash display when alarm is active
57
10
Lower limit setting for pickup stall timeout. Set for 10 seconds.