CTRIO Initialize Preset Table on Reset (CTRINTR) (IB-1010)
CTRIO Initialize Preset Table on Reset, on a leading edge transition to this IBox, will create a
single entry Preset Table in memory but not as a file, on a specific CTRIO Output
resource.This IBox will take more than 1 PLC
scan to execute. Either the Success or Error
bit will turn on when the command is
complete. If the Error Bit is on, you can use
the CTRIO Read Error Code (CTRRDER)
IBox to get extended error information.
Entry Type:
K0: Set
K1: Reset
K2: Pulse On (uses Pulse Time)
K3: Pulse Off (uses Pulse Time)
K4: Toggle
K5: Reset Count
Note that the Pulse Time parameter is ignored by some Entry Types.
The Workspace register is for internal use by this IBox instruction and MUST NOT be used
anywhere else in your program.
CTRINTR Parameters
• CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config
Ibox)
• Output#: specifies a CTRIO output to be used by the instruction
• Entry Type: specifies the Entry Type to add during the edit
• Pulse Time: specifies a pulse time in msecs for the Pulse On and Pulse Off Entry Types
• Preset Count: specifies an initial count value to begin at after Reset
• Workspace: specifies a V-memory location that will be used by the instruction
• Success: specifies a bit that will turn on once the instruction has successfully completed
• Error: specifies a bit that will turn on if the instruction does not complete successfully
DS5