DL205 User Manual, 4th Edition, Rev. B
5–109
Chapter 5: Standard RLL Instructions - Math
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Add Formatted (ADDF)
Add Formatted is a 32-bit instruction that adds the BCD value
in the accumulator with the BCD value (Aaaa) which is a range
of discrete bits. The specified range (Kbbb) can be 1 to 32
consecutive bits. The result resides in the accumulator.
NOTE:
Status flags are valid only until another instruction uses the same flag.
In the following example, when X6 is on, the value formed by discrete locations X0–X3 is
loaded into the accumulator using the Load Formatted instruction. The value formed by
discrete locations C0–C3 is added to the value in the accumulator using the Add Formatted
instruction. The value in the lower four bits of the accumulator is copied to Y10–Y13 using
the Out Formatted instruction.
ý
ý
ý
þ
230
240
2
5
0
-1
2
6
0
ADDF
A aaa
K bbb
Operand Data Type
DL260 Range
A
aaa
bbb
Inputs X
0-1777
-
Outputs Y
0-1777
-
Control Relays C
0-3777
-
Stage Bits S
0-1777
-
Timer Bits T
0-377
-
Counter Bits CT
0-377
-
Special Relays SP
0-777
-
Global I/O GX/GY
0-3777
-
Constant K
-
1-32
Discrete Bit Flags
Description
SP63
On when the result of the instruction causes the value in the accumulator to be zero.
SP66
On when the 16-bit addition instruction results in a carry.
SP67
On when the 32-bit addition instruction results in a carry.
SP70
On anytime the value in the accumulator is negative.
SP75
On when a BCD instruction is executed and a NON-BCD number was encountered.
Direct
SOFT
LDF
X0
K4
X6
Load the BCD value represented
by discrete locations X0–X3
into the accumulator
ADDF
C0
K4
Add the BCD value in the
accumulator with the value
represented by discrete
location C0–C3
OUTF
Y10
K4
Copy the lower 4 bits of the
accumulator to discrete
locations Y10–Y13
+
0 0 0 0 0 0 0
8
(C0-C3)
(Accumulator)
3
X0
X1
X2
X3
OFF
OFF
OFF
ON
C0
C1
C2
C3
ON
ON
OFF
OFF
Y10
Y11
Y12
Y13
ON
OFF
OFF
OFF
The unused accumulator
bits are set to zero
Acc.
Handheld Programmer Keystrokes
STR
$
SHFT
3
D
3
D
OUT
GX
SHFT
5
F
0
A
4
E
ENT
6
G
ENT
1
B
4
E
0
A
ENT
SHFT
ANDST
L
3
D
0
A
4
E
ENT
5
F
5
F
0
A
NEXT
NEXT
NEXT
NEXT
0
1
1
0 0
0 0 0
DS
Used