ANLGCMB Example
In the following example, the ANLGCMB instruction is used to set up the pointer method
for an analog I/O combination module that is installed in option slot 2. Four input channels
are enabled and the analog data will be written to V2000 - V2003 in BCD format. Two
output channels are enabled and the analog values will be read from V2100 - V2101 in BCD
format.
NOTE
: An Analog I/O IBox instruction is used without a permissive contact. The top line will be identified in
BOLD italics
, and the instruction name and ID will be in
BOLD characters.
No permissive contact
or input logic is used
with this instruction
Parameter
DL205 Range
Base # (K0-Local) . . . . . . . . . . . . . . . . . . . . . . . K
K0-3
Slot # . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
K0-7
Number of Input Channels . . . . . . . . . . . . . . . . K
K1-8
Input Data Format (0-BCD 1-BIN) . . . . . . . . . . . K
BCD: K0; Binary: K1
Input Data Address . . . . . . . . . . . . . . . . . . . . . . V
See DL205 V-memory map - Data Words
Number of Output Channels . . . . . . . . . . . . . . . K
K1-8
Output Data Format (0-BCD 1-BIN) . . . . . . . . . K
BCD: K0; Binary: K1
Output Data Address . . . . . . . . . . . . . . . . . . . . . V
See DL205 V-memory map - Data Words