Off Delay Timer (OFFDTMR) (IB-302)
Off Delay Timer will delay the "turning off" of the Output parameter by the specified Off
Delay Time (up to 99.99 seconds) based on the power flow into the IBox. Once the IBox
receives power, the Output bit will turn on
immediately. When the power flow to the
IBox turns off, the Output bit WILL
REMAIN ON for the specified amount of
time (in hundredths of a second). Once the
Off Delay Time has expired, the output will
turn Off. If the power flow to the IBox comes
back on BEFORE the Off Delay Time, then
the timer is RESET and the Output will
remain On - so you must continuously have
NO power flow to the IBox for AT LEAST
the specified Off Delay Time before the Output will turn Off.
This IBox utilizes a Timer resource (TMRF), which cannot be used anywhere else in your
program.
OFFDTMR Parameters
• Timer Number: specifies the Timer(TMRF) number which is used by the OFFDTMR instruction
• Off Delay Time (0.01sec): specifies how long the Output will remain on once power flow to the
Ibox is removed (up to 99.99 seconds).
• Output: specifies the output that will be delayed “turning off ” by the Off Delay Time.
Parameter
DL205 Range
Timer Number . . . . . . . . . . . . . . . . . . . . . . . . . T
T0-377
Off Delay Time . . . . . . . . . . . . . . . . . . . . . . . . K,V
K0-9999; See DL205 V-memory map - Data Words
Output . . . . . . . . . . . . . . . . . . . . X, Y, C, GX,GY, B
See DL205 V-memory map