DL205 User Manual, 4th Edition, Rev. B
5–308
Chapter 5: Intelligent Box (IBox) Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
ECOM100 Write IP Address (ECWRIP) (IB-723)
ECOM100 Write IP Address will write the given IP Address to the ECOM100 module on a
leading edge transition to the IBox. See also ECOM100 IP Setup (ECIPSUP) IBox 717 to
setup ALL of the TCP/IP parameters in a single
instruction - IP Address, Subnet Mask, and
Gateway Address.
The Workspace parameter is an internal, private
register used by this IBox and MUST BE
UNIQUE in this one instruction and MUST
NOT be used anywhere else in your program.
Either the Success or Error bit parameter will
turn on once the command is complete. If there
is an error, the Error Code parameter will report
an ECOM100 error code (less than 100), or a
PLC logic error (greater than 1000).
The IP Address is stored in Flash-ROM in the ECOM100 and the execution of this IBox will
disable the ECOM100 module for at least a half second until it writes the Flash-ROM.
Therefore, it is HIGHLY RECOMMENDED that you only execute this IBox ONCE on the
second scan. Since it requires a LEADING edge to execute, use a NORMALLY CLOSED
SP0 (STR NOT First Scan) to drive the power flow to the IBox.
In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the
ECOM100 circuit board.
ECWRIP Parameters
• ECOM100#: this is a logical number associated with this specific ECOM100 module in the
specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must
reference this logical number
• Workspace: specifies a V-memory location that will be used by the instruction
• Success: specifies a bit that will turn on once the request is completed successfully
• Error: specifies a bit that will turn on if the instruction is not successfully completed
• Error Code: specifies the location where the Error Code will be written
• IP Address: specifies the IP Address that will be written to the module
DS5
Used
HPP
N/A
Parameter
DL205 Range
ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
K0-255
Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
See DL205 V-memory map - Data Words
Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
See DL205 V-memory map
Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
See DL205 V-memory map
Error Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
See DL205 V-memory map - Data Words
IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.0.0.1. to 255.255.255.254