DPM3 User Manual, 1st Edition
User Manual - DPM3 Series Panel Meters
32
Technical Specifications
Technical Specifications
Process
Range
Input Impedance
Accuracy
Resolution
±10VDC
1MΩ
±(0.1% rdg + 1 digit)
1mV
±20mA DC
15Ω
±(0.1% rdg + 1 digit)
1µA
Sensor
Excitation
24V@60mA, 10V @ 60mA
Potentiometer
Range
Input Impedance
Accuracy
Resolution
200Ω minimum
1MΩ
±(0.1% rdg + 1 digit)
0.005%
Sensor
Excitation
10V @ 60mA
Load Cell
Range
Input Impedance
Accuracy
Resolution
±15mV, ±30mV,
±150mV
100MΩ
±(0.1% rdg + 1 digit)
1µV
Sensor
Excitation
10V @ 60mA
Temperature
RTD
Pt100 (3-Wire)
Fixed display
range /
resolution
-200.0°C to 800.0°C / 0.1°C
-200°C to 800°C / 1°C
-328.0°F to 1472.0°F/ 0.1°F
-328°F to 1472°F / 1°F
Accuracy /
resolution
±(0.2% rdg+0.6°C) / 0.1°C
±(0.2% rdg+1°C) / 1°C
±(0.2% rdg+1°F) / 0.1°F
±(0.2% rdg+2°F) / 1°F
Pt100 sensor
excitation
<1mA DC
Max lead
resistance
40Ω / cable (balanced)
Thermocouple
J
K
T
N
Fixed display
range /
resolution
-150.0°C to
1100.0°C / 0.1°C
-150°C to
1100°C / 1°C
-238.0°F to
2012.0°F / 0.1°F
-238°F to
2012°F / 1°F
-150.0°C to
1200.0°C / 0.1°C
-150°C to
1200°C / 1°C
-238.0°F to
2192.0°F / 0.1°F
-238°F to
2192°F / 1°F
-200.0°C to
400.0°C / 0.1°C
-200°C to
400°C / 1°C
-328.0°F to
752.0°F / 0.1°F
-328°F to
752°F / 1°F
-150.0°C to
1300.0°C / 0.1°C
-150°C to
1300°C / 1°C
-238.0°F to
2372.0°F / 0.1°F
-238°F to
2372°F / 1°F
Accuracy /
resolution
±(0.4% rdg+0.6°C) / 0.1°C
±(0.4% rdg+1°C) / 1°C
±(0.4% rdg+1°F) / 0.1°F
±(0.4% rdg+2°F) / 1°F
±(0.4% rdg+0.6°C) / 0.1°C
±(0.4% rdg+1°C) / 1°C
±(0.4% rdg+1°F) / 0.1°F
±(0.4% rdg+2°F) / 1°F
±(0.4% rdg+0.6°C) / 0.1°C
±(0.4% rdg+1°C) / 1°C
±(0.4% rdg+1°F) / 0.1°F
±(0.4% rdg+2°F) / 1°F
±(0.4% rdg+0.6°C) / 0.1°C
±(0.4% rdg+1°C) / 1°C
±(0.4% rdg+1°F) / 0.1°F
±(0.4% rdg+2°F) / 1°F
Cold junction
compensation
range
-10°C to 60°C (14°F to 140°F)
Offset
programmable
-19.9° / +99.9°