DPM3 User Manual, 1st Edition
User Manual - DPM3 Series Panel Meters
22
MAX/MIN function
With the meter in
RUN
mode: Activated after pressing the
SHIFT
key. From
RUN
mode, a
press shows the maximum value read by the instrument since the last time it has been switched
on, unless a
RESET MAX/MIN
is done, the
MAX
led will light up. A second press shows the
minimum value in the same conditions as before, with the consequent minimum indication
through the
MIN
led. A third press brings the instrument back to
RUN
mode.
Reset MAX/MIN
With the meter in
RUN
mode: Pressing the
SHIFT
key for 3 seconds, while the meter shows
the peak value
(MAX)
, will produce a reset of the value. Pressing
SHIFT
key for 3 seconds
while the meter shows the valley value
(MIN)
will produce a reset of the value.
Configuration Lockout
In mode
RUN
if the
ENTER
key is pressed for 3 seconds, the meter will show the indication
CodE
, and following
0000
, allowing the user to introduce the security code. If the code that
has been introduced is wrong, the meter will go back to
RUN
mode, if it is correct, it will
allow the access to the security menu. See section detailing Configuration Lockout.
Programming Mode
One press on the
ENTER
key will bring the instrument to the Programming Mode
-Pro-
mode.
Return to Factory Configuration
After accessing programming mode,
Pro
. Allows entering a code of access to the reset of the
configuration parameters, this code is 74. When entering this code the instrument shows the
LoAdIng dEFAuLt ConFIGurAtIon
legend, and then
StorE
, which means that they have
been stored in the non volatile memory of the meter.
Factory configuration
INPUT: Process 0 - 10V
DISPLAY
Input 1: +00.000 Display 1: +00.000
Input 2: +10.000 Display 2: +10.000
Filter P: 0
Round 01
Tare mode: 1
Brightness: High
DISPLAY COLORS Run Mode: Green, Prog Mode.: Amber
SETPOINTS
Setpoint 1: +01.000, Setpoint 2: +02.000
Setpoint 3: +03.000, Setpoint 4: +04.000
Compared with: Net
Mode: HI
Dly: 00.0
Alarm Color: No Change
ANALOG OUTPUT CONFIGURATION
Display HI: +10.000
Display LO: +00.000
LOGIC FUNCTIONS PIN 2=function 1, PIN 3=function 2 and
PIN 4=function 6
-
-
3s?
=74?