AMP TRAVEL SETUP (cont)
STEP 5A. (cont)
Using the Up / DOWN keys drive the motor into the close and
open stops and adjust the stop curent trip levels. The motor should
be driven into each mechincal stop at full speed until the con-
troller senses a current trip and stops the motor.
Note: If the motor drives in the wrong direction (UP closes gate
/ DOWN opens gate) the motor wires need to be swapped over.
The trip current for each direction can be view and adjusted by
pressing the NEXT key on the keypad.
See PARAMETER VIEW AND EDIT for adjustement procedure.
STEP 6A. CONFIRMING SETTINGS
When the settings have being adjusted correctly, drive the gate to
the open stop and then press the SET Key.
As step 7A requires the gate to be open, the controller will pro-
mopt you to confirm the gate leaf is in the open position. Press
SET to confirm or press EXIT to go back and drive the gate open.
STEP 7A. AUTOMATIC PROFILING
After a brief pause the controller will automatically close and
open gate several times and learn the gates load and travel
characteristics. When the setup is complete the MAIN SCREEN
will be displayed with the gate shown to be OPEN. The Gate can
now be used.
/
/\
\\
\/
/
M1(2)
to
Test
Stop
AMPS,
SET
PRESS
Testing The Stop Detection Settings
OR
PRESS
PRESS
PRESS
PRESS
Accessing the Stop Detection Settings
Press
>
to
Adjust
Stop
AMPS
Stop Detection Settings
M1(2)
OPN(CLS)
Limit
AMPS
2.0
/
/\
\\
\/
/
M1(2)
to
Test
Stop
AMPS,
SET
PRESS
Confiming Stop Current trip settings
OR
PRESS
9
PRESS
Confirming Gate is Open
At
Open
Limit?
Press
SET
if
ok.
Reprofiling is a simplified way of re-learning the travel charastics of a previously setup Limit Switch/AMP travel installation. Re-pro-
filing can be used when the travel limits of a gate are altered or when the travel characteristics of the gate change due to mechnical
adjustments etc. To initiate a re-profile simply locate “MENU 10.3 Reprofile Travel” and press SET then follow the prompts. The
reprofile feature will also be automatically started when a control parameter is altered which affects the gates travel. Reprofile is not
avaiable for TIMED TRAVEL installations.
RE-PROFILING TRAVEL