400 Series Installation and Configuration
DCU 410 Engine Panel Installation
69
Oscillating Feedback time
Set the timer for oscillating feedback failed warning.
Auto Start/Stop
The DCU can start the engine automatically. The following
conditions must be met:
Terminal 88 (Automatic Mode) must be high (24V),
or the DCU menu item Settings
–
Automatic must
be selected.
Terminal 89 (Automatic Start) must be high (24V).
This triggers the start sequence.
Initial Start Delay
When the start sequence activates, this timer must elapse
before the DCU will do the first start attempt.
Typical setting:
1 second
No. of Start Attempts
The total number of start attempts.
Typical setting:
3 attempts
Prelube Before Each Start Attempt
Select Yes to prelube before each start attempt.
Select No to prelube before the first attempt only.
Starter 1 / Starter 2
Cranking Time
The time the starter engine is engaged.
Typical setting:
5-7 seconds
Delay Between Start Attempts
If the engine did not start after the previous attempt, it
will delay this many seconds until it does the next start
attempt.