400 Series Installation and Configuration
DCU 410 Engine Panel Installation
67
5 RPM
300 RPM
Prelube
The DCU can prelube the engine at certain regular
intervals, and/or before start.
Prelube Type
–
Fixed Time
This will activate prelube on terminal 84 (Prelube Act.) for
a fixed time, after which the DCU will crank the engine
with terminal 83 (Crank).
Prelube Time
Set the number of seconds the DCU shall prelube before
start.
Typical setting:
5-30 seconds
Prelube Type
–
Until Pressure
This will activate prelube on terminal 84, then await the
activation of the Prelube Complete signal on terminal 86.
Prelube Timeout
The DCU expects to receive the Prelube Complete signal
on terminal 86 within this timer period.
Typical setting:
5-30 seconds