32
DCU 410 Engine Panel Installation
400 Series Installation and Configuration
The components in Marine Pro, including the DCU, uses
fixed (not dynamic) IP-addresses, which must be set
manually.
To connect to the DCU
1.
Connect an Ethernet cable between your laptop
and the DCU port COM 6 (Ethernet port).
2.
In the DCU menu, select Version Information. Note
the IP-address. From factory, the IP-address is
192.168.0.101.
3.
In your web browser, type the IP-address, eg.
http://192.168.0.101
in the address field.
4.
Press Enter, and note the login screen.
5.
In the login screen, type
- Username = dcu
- Password = 1234 (from factory)
Note! If the password is unknown, then use the
Encrypted PIN and send this to
service@auto-
maskin.com
to obtain the correct PIN.
Logged In?
Proceed to the Web Server Configuration chapter, page
35.
Not Logged In?
Continue with connection settings as described below.
Further connection settings
Change the IP-address of the DCU
If necessary, the IP-address of the DCU can easily be
changed.
Note! The last digit in the IP-address becomes the engine
number.
The DCU has a fixed IP-address that is set during the first
power-on set up. The IP-address may also be changed
later, in the DCU panel menu:
Menu / Settings / Administration (locked/open) /
Miscellaneous / Network