7.7 Temperature derating

The output power of the inverter varies with ambient temperature, as shown in the figure below.

7.8 External fan

The inverter’s external fans switch on automatically when cooling via the heat sink is no longer

sufficient. When the inverters core temperature reaches 70°C, the fan will be activated. It will

switch off once the core temperature is below 60°C.

Installation is recommended either in covered open-air spaces or inside in spaces with enough

ventilation. Failing to do so will impact the maximum performance of the inverter.

M-S2-OX-EN-V2.4

39

Содержание OX Series

Страница 1: ...Installation and Operation Manual Solar Inverters OX series Autarco Group B V IM S2 OX EN V2 4...

Страница 2: ...anual is an integral part of the unit Please read the manual carefully before installation operation or maintenance Keep this manual for future reference Product information is subject to change witho...

Страница 3: ...lation 14 5 1 Safety 14 5 2 Appropriate mounting location 14 5 3 Mounting instructions 15 5 4 Mounting and dimensions 16 5 5 Safety clearance 17 5 6 Mounting procedure 18 5 6 1 Wall mounting 18 5 6 2...

Страница 4: ...evices 41 8 3 Registration 42 9 Maintenance 43 9 1 Fan Maintenance 43 10 Recycling and Disposal 45 11 Troubleshooting 46 11 1 General 46 11 2 Alarm messages internal components system and design fault...

Страница 5: ...rter RISK OF ELECTRIC SHOCK Indicates important safety instructions which if not correctly followed could result in electric shock HOT SURFACE Indicates safety instructions which if not correctly foll...

Страница 6: ...m code or SKU will include an additional number at the end The final number references the default grid standard and colour of inverter For example S2 OX80000S 1 is the 80kW model with Dutch grid stan...

Страница 7: ...ion please don t touch the heat sink or peripheral surface during or shortly after operation NOTICE Do not directly connect AC output of the inverter to any private AC equipment The PV inverter is des...

Страница 8: ...module strings from the inverter 2 4 Explanations of symbols on inverter 10min DANGER HIGH ELECTRIC VOLTAGE This device is directly connected to public grid All work to the inverter shall be carried...

Страница 9: ...NOT be disposed of in residential waste Please go to chapter 10 Recycling and Disposal for proper treatments CE MARK This equipment conforms to the basic requirements of the EU guideline governing lo...

Страница 10: ...tions Key features Maximum efficiency of 98 7 Wide MPPT voltage range Low turn off voltage High enclosure protection class IP66 Intelligent redundant fan cooling Standard 5 year product warranty exten...

Страница 11: ...anual 3 3 Product overview A Inverter cover B LED light POWER C LED light OPERATION D LED light ALARM E Display F Escape key G Up key H Down key I Enter key J DC switches K DC inputs L Meter M AC outp...

Страница 12: ...fore this manual divides specifications for the two variations referred to as group 1 and group 2 Group 1 includes the models OX80000 S OX110000 HV S Group 2 includes the models OX100000 S OX110000 S...

Страница 13: ...for moving the inverter 2 Open the carton then two people handle both sides of the inverter through the area denoted dotted line Due to the weight of the inverter bruises or bone fractures could occur...

Страница 14: ...5 2 Appropriate mounting location The heat sink can reach a temperature of 75 C under operation Location and environmental requirements Make sure the mounting wall is strong enough to hold the weight...

Страница 15: ...o people are required to remove the inverter from the carton and install the inverter Handles are formed into the heatsink for ease of handling the inverter The inverter is suitable for outdoor and in...

Страница 16: ...llations below 5 4 Mounting and dimensions The inverter can be mounted to the wall or metal array racking The mounting holes should be consistent with the size of the bracket or the dimensions Dimensi...

Страница 17: ...ION Make sure heat sinks are out of reach WARNING When installing multiple inverters make sure there is sufficient clearance between them Staggered installation may be recommended High temperatures ma...

Страница 18: ...5 6 Mounting procedure 5 6 1 Wall mounting 1 Mount the wall bracket onto the mounting wall with appropriate screws plugs 2 Lower the inverter onto the bracket 18 OX series Inverters...

Страница 19: ...eration manual 3 Use screws in the packaging to fix the bottom of the inverter to the mounting bracket 5 6 2 Rack mounting 1 Mount the wall bracket onto the mounting rack with appropriate screws plugs...

Страница 20: ...2 Lower the inverter onto the bracket 3 Use screws in the packaging to fix the bottom of the inverter to the mounting bracket 20 OX series Inverters...

Страница 21: ...t need to be opened during DC electrical connection MC4 connector The labels located at the bottom of the inverter are described below in the table All electrical connections meet local and national s...

Страница 22: ...nded to use the 25 50mm outdoor copper core cable The grounding cable should be at least half the size of the AC wiring 2 Prepare OT terminals M10 IMPORTANT For multiple inverters in parallel all inve...

Страница 23: ...mp to crimp the terminal to the wire as shown in the figure below IMPORTANT After crimping the terminal to the wire inspect the connection to ensure the terminal is solidly crimped to the wire 5 Remov...

Страница 24: ...ormed only after receiving authorization from the utility that operates the grid WARNING An overcurrent protection device OCPD must be used between the inverter and the grid The AC cable used must be...

Страница 25: ...r cored cable Traverse cross sectional area mm Range 35 185 Recommended 70 Cable outer diameter mm Range 38 56 Recommended 45 NOTE Use M10 OT terminals The steps to assemble the AC grid terminals are...

Страница 26: ...sfer terminal in order to avoid direct contact between the copper bar and the aluminum alloy cable Please select a copper aluminum transfer terminal based on your cable specification 3 Leave the AC br...

Страница 27: ...al NOTICE It is important that the AC wires are connected to the right terminals as indicated by the L N and Ground symbols on each AC connector In some countries a second protective conductor is requ...

Страница 28: ...110000 HV S 540V 110 160 The Autarco inverter is equipped with an integrated Residual Current Protective Device RCPD and Residual Current Operated Monitor RCOM The RCOM will detect the leakage current...

Страница 29: ...OX110000 HV S 10 132000W DANGER Do not connect the strings with an open circuit voltage greater than the Max DC voltage of the inverter To connect the PV generator to the inverters we use 4mm or 6mm...

Страница 30: ...assembly other than those listed in the MC4 connector manual neither safety nor compliance with the technical data can be guaranteed 6 6 Inverter commissioning sequence Turn ON Turn OFF 1 Connect AC s...

Страница 31: ...mally When the inverter DC switch and AC switch have been turned on the inverter will start initializing After approx 3 minutes the inverter will start normal operation with the inverter display showi...

Страница 32: ...3 V_DC04 VALUE V I_DC04 VALUE A Shows the input voltage V of the MPPT4 Shows the input current A of the MPPT4 V_DC05 VALUE V I_DC05 VALUE A Shows the input voltage V of the MPPT5 Shows the input curre...

Страница 33: ...8 of the inverter I_DC01 VALUE A I_DC02 VALUE A Shows the input current A of the DC input 1 Shows the input current A of the DC input 2 I_DC03 VALUE A I_DC04 VALUE A Shows the input current A of the...

Страница 34: ...n be scrolled through with UP DOWN keys to see the information as per the table below Press ENTER key to enter a submenu Press ESC key to go back to the main menu Alarm Messages The display shows the...

Страница 35: ...d Settings WARNING Access to this section of the menu is for Autarco qualified and accredited technicians only Unauthorized access will void the product warranty and any kWh Guarantee Screen can be sc...

Страница 36: ...h output to zero Using this function without previous approval from Autarco will void any existing kWh Guarantees New Password Change the password to enter Advanced Info and Advanced Settings Enter th...

Страница 37: ...Priority 6 Initial Settings 7 Voltage PCC Set Restore Settings Restore Settings resets the inverter to factory defaults HMI Updater Selecting HMI Updater will show the current software version the LCD...

Страница 38: ...I V Curve Used to create I V curves for all DC inputs 1 Set I V curve 2 I V curve scan 38 OX series Inverters...

Страница 39: ...ch on automatically when cooling via the heat sink is no longer sufficient When the inverters core temperature reaches 70 C the fan will be activated It will switch off once the core temperature is be...

Страница 40: ...for WiFi Cellular datalogger COM2 and COM3 Cable glands and cover with following connection points behind o 2 x RJ45 connections o 1 x RS485 terminal block COM2 and COM3 are RJ 45 connectors suitable...

Страница 41: ...nd in D are enabled for digital O M features Steps for using RJ45 connections for RS485 Communications 1 Use a network wire stripper to strip the insulation layer off the communication cable Using the...

Страница 42: ...kWh Guarantee for your system please ensure that the following is completed and recorded on site before you leave Inverter and module serial numbers unless a specific order was made for the system in...

Страница 43: ...bility to dissipate heat Any dirt or dust can be removed with a cloth or soft brunch 9 1 Fan Maintenance If the fan does not work properly the inverter will not be cooled effectively and inverter effi...

Страница 44: ...8 Connect the electrical wire and reinstall the fan assembly Restart the inverter The fans must be tested at least once per year and cleaned if necessary by qualified personnel 44 OX series Inverters...

Страница 45: ...Electrical and Electronic Equipment and its implementation as national law electrical equipment that has reached the end of its life must be collected separately and returned to an approved recycling...

Страница 46: ...Check if PV is reversed LCD show initia lizing all the time Can not start up 1 Check if the connector on main board or power board are fixed 2 Check if the DSP connector to power board are fixed OV DC...

Страница 47: ...protection model with AFCI module Detect arc in DC circuit 1 Check inverter connection whether arc exists and restart inverter Reve DC One of the DC string is reversely connected 1 Please check the i...

Страница 48: ...he protection limit if it s allowed by electrical company OV G F01 02 Over grid frequency UN G F01 02 Under grid frequency G IMP High grid impedance NO GRID No grid voltage 1 Check connections and gri...

Страница 49: ...8000 110000 121000 121000 Nominal AC current A 121 6 152 0 167 1 117 6 Max AC current A at 380V 133 7 167 1 183 8 129 4 Max AC current A at 400V 129 4 158 9 174 8 129 4 at 540V Power connection Three...

Страница 50: ...ccording to EN61000 6 2 EN61000 6 4 AS3100 IEC62109 General data Dimensions W x H x D mm 1050 x 567 x 286 5 Weight 82kg Installation environment Indoor or outdoor Mounting Wall bracket Operating tempe...

Отзывы: